Factory Settings Parameters, page 6 of 9
Parameter
Menu
SMALL DISPLAY
Line
(Large Display)
A145
(Password)
HUM TYPE
A146
(Humidifier Model)
HUM VOLTAGE
A147
(Humidifier Voltage)
HUM LAST (Humidity in
A148
Last xxx Hours)
A149
PREFILL (Prefill Time)
A150
FILL (Fill Time)
HUM ON
A151
(Humidifier On Time)
DEH COMP
A152
(Dehumidification with
C
)
iCOM
ADVANCED MENU's Continued
Default
-
NO (No)
-
15 hours
IFS = 30 sec
IFL = 60 sec
IFS = 30 sec
IFL = 60 sec
IFS = 8 min
IFL = 10 min
1
117
Control Training and Service Manual
Range
-
NO, EXT, IFS, IFL,
PEX6, PEX9, PEX12,
21LLA, 53LLC, 53HLB,
93LLE, 93HLD, d3H,
HT2, HT5, HT9 (No,
External, IFS, IFL,
PeX @ 6 Amp,
PeX @ 9 Amp,
PeX @ 12 Amp,
21L-CLA, 53L-CLC,
53H-CLB, 93L-CLE,
93H-CLD, d3H,HT2,
HT5, HT9)
Volts
1 – 120 hours
1 – 120 sec
1 – 120 sec
1 - 3600 sec
1, 2, Both
Control
Board
Safe
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF