Emerson Liebert iCOM Training And Service Manual page 84

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

* Note: Menu line S103 – Control type selection for PID and Menu line S106 -
Temperature Derivative Time parameters appear on the display but are not active
at this time.
Setpoint Parameters, page 2 of 3
Parameter
Menu
SMALL DISPLAY
Line
(Large Display)
S112
(Password)
HUM SET
S113
(Humidity Setpoint)
HUM CTRL
S114
(Humidity Control
Type)
HUM PB (Humidity
S115
Proportional Band)
HUM INT (Humidity
S116
Integration Time)
HUM DB
S117
(Humidity Deadband)
LO LIM 1 (Dehum/Heat
S118
Low Limit 1) *
LO LIM 2 (Dehum/Heat
S119
Low Limit 2) *
* Note: Menu line S118 – Low Limit 1 is for Compressor 1 control during
dehumidification. The return air temperature will not decrease below this
programmed value during dehumidification. If the return air temperature
decreases to this programmed value Compressor #1 will stop dehumidification
until the return air temperature increases above this value. Menu line S119 – Low
Limit 2 performs the same function for Compressor 2 during dehumidification.
iCOM
SERVICE MENU's Continued
Default
-
50%
PRED
(Predictive)
10%
0 min
0%
-3.4°F
-7°F
83
Control Training and Service Manual
Shared
Range
in TW1
-
1 - 80%
Yes
REL, COMP,
PRED
(Relative,
Yes
Compensated,
Predictive)
1 – 20%
Yes
0 – 15 min
Yes
0 – 50%
Yes
(-9.9) – (-2.0°F)
No
(-9.9) – (-2.0°F)
No
Control
Board
Safe
-
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF