Page 3
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and Emerson makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein.
Quick Start Guide Section 1 GFK-2941K Sep 2019 1. User Features The PACSystems RX3i CPE330 is a richly featured programmable controller CPU Figure 1: IC695CPE330 Features at a equipped with 1GHz dual-core Glance microprocessor, 64Mbytes built-in program memory and two independent high-speed Ethernet interfaces.
Page 5
Quick Start Guide Section 1 GFK-2941K Sep 2019 support for up to 32 I/O devices and update rates of 1 – 512ms. I/O device update rates of 8ms and faster are possible with 16 or fewer devices. When there are more than 16 devices configured, update rates of 16ms and higher are available.
Page 6
HART device connected to an RX3i Analog module in an IC695PNS001 RX3i PROFINET Scanner. A UDFB that automates the COMMREQ control logic is available for download from the Emerson support website. (Refer to New Features and Enhancements for additional information.)
Quick Start Guide Section 1 GFK-2941K Sep 2019 signals are decoded by the PNS101 using either an IC695HSC304 or IC695HSC308 High Speed Counter Module. SoE recording is available in both simplex and redundant PROFINET systems. • User may program in Ladder Diagram, Structured Text, Function Block Diagram, or •...
Page 8
Quick Start Guide Section 1 GFK-2941K Sep 2019 The CPU runs with I/O User program memory is Run I/O sweep enabled. read only. The CPU runs with User program memory is outputs disabled. read only. The CPU is not allowed to User program memory can Stop go into Run mode.
Quick Start Guide Section 1 GFK-2941K Sep 2019 1.2. Light-Emitting Diode Indicators (LEDs) Status Indicators LED State Operating State CPU OK On Green CPU has passed its power-up diagnostics and is functioning properly. (After initialization sequence is complete.) Power is not applied, or CPU has a problem, which may be indicated by blink pattern.
Page 10
Quick Start Guide Section 1 GFK-2941K Sep 2019 LED State Operating State No Overrides active in I/O Reference Tables. RDSD On Green USB Device detected (No Activity) Blinking Port activity detected on USB Interface Green No port activity detected on USB Interface On Red RDSD Failure Blinking...
Quick Start Guide Section 1 GFK-2941K Sep 2019 LED State Operating State Corresponding network data speed is 100 Mbps or 10 Mbps. 1.3. Ethernet Ports LAN1 connects to the uppermost RJ-45 connector. It is not switched. LAN2 connects to the two lower RJ-45 connectors. They are switched internally. Record the IP Address of each LAN in the space provided (Figure-1).
Page 12
Quick Start Guide Section 1 GFK-2941K Sep 2019 IP Address: 192.168.0.100 10.10.0.100 Subnet 255.255.255.0 255.255.255.0 Mask: Gateway: 0.0.0.0 0.0.0.0 Figure 2: Typical Multi-tier LAN Application A typical application will take advantage of the two independent LANs. The dedicated LAN1 port will be used for communications with plant-level or supervisory layers. The User Features...
Page 13
Quick Start Guide Section 1 GFK-2941K Sep 2019 switched LAN2 will typically be used to communicate with devices within the manufacturing cell or process, including local HMI devices and micro-controllers. User Features...
As the consignee, it is your responsibility to register a claim with the carrier for damage incurred during shipment. Emerson will fully cooperate with you, however, should such action be necessary. After unpacking the RX3i equipment, record all serial numbers. Serial numbers are required if you should need to contact Customer Care during the warranty period.
Quick Start Guide Section 2 GFK-2941K Sep 2019 If you need technical help, contact Technical Support. For phone numbers and email addresses, refer to the back cover of this Guide. 2.3. Installation in Hazardous Areas The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive atmospheres: CLASS 1 DIVISION 2 GROUPS ABCD •...
Page 16
Quick Start Guide Section 2 GFK-2941K Sep 2019 Energy Pack (IC695ACC402) is connected, its ground-strap must be grounded as described in PACSystems RX3i Energy Pack IC695ACC402 Quick Start Guide, GFK-2939. Hardware Installation...
Quick Start Guide Section 3 GFK-2941K Sep 2019 3. Module Start-up 3.1. You Will Need: • An RX3i Universal Backplane: IC695CHS007, IC695CHS012 or IC695CHS016. • This PACSystems RX3i CPU. This CPU occupies two backplane slots. • An RX3i rack-mounted Power Supply Module and compatible power source or DC).
Quick Start Guide Section 3 GFK-2941K Sep 2019 2. If used, mount the compatible RX3i Energy Pack (IC695ACC402) within 3 feet of the CPU. The dedicated interconnect cable attaches to the underside of CPE330. Follow interconnect and grounding instructions in PACSystems RX3i Energy Pack IC695ACC402 Quick Start Guide, GFK-2939.
Quick Start Guide Section 3 GFK-2941K Sep 2019 To enable redundancy in a CPE330 project, select the CPE330 target in the PME Navigator and use the Property Inspector to change the Enable Redundancy target property to True. 3.4. PROFINET Controller Configuration PROFICY Machine Edition 8.60 SIM 13, PME 9.00 SIM 4 or later may be used to configure an Embedded PROFINET Controller in the CPE330 Hardware Configuration on LAN 2.
Page 20
Quick Start Guide Section 3 GFK-2941K Sep 2019 Hold down the RDSD UPLD button and turn power on to the CPE330. Continue to depress the RDSD UPLD button until the CPE330 powers up and displays one of the following patterns on the LEDs. CPU Status Indicators CPE330 LED LED State...
The compatibility setting may be viewed at any time using the CPE330’s firmware update web page. When the compatibility setting is Normal (CPU320), the catalog number is listed as “IC695CPE330”. When the compatibility setting is CRU320 compatibility mode, the catalog number is listed as “IC695CPE330 CRU320 Compatibility Mode”.
Quick Start Guide Section 4 GFK-2941K Sep 2019 4. Periodic Maintenance Figure 3: RTC 4.1. Real-Time Clock Battery Battery The CPE330 is shipped with a real time clock (RTC) battery installed (see Figure-3). Over time, this battery will need to be replaced.