Figure 46: Basic Setup Diagram
4.3

Initial Start-up

You will need the following:
Safety Extra Low Voltage (SELV) and Limited Energy Circuit or SELV and Class 2 dc
power supply.
The power terminal block is supplied with the product. For voltage and requirements,
refer to the Input Power specifications for each individual product in Section 1.1,
Specifications.
The mating power terminal block supports stranded 30 to 14 AWG (0.05 to 2.00
mm2) wires. The user calculates proper gauge wiring for current carrying capacity and
loss according to local regulations.
At a minimum, the cable must be rated for 75°C (167°F), or more.
USB-compatible keyboard (optional)
USB-compatible mouse (optional)
4.3.1

Connecting Input Power

To connect input power:
1.
2.
3.
4.
5.
Solid amber while the QuickPanel+ is starting up
Solid green during normal operation
Pre-installation Checks
Verify that the power cable is not energized.
Loosen the screw clamps on the mating power connector.
Strip the insulation from the power cables.
Secure the power cable to the mating connector, noting polarity, and tighten the
screw clamps. The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
Apply dc power to the unit. During normal startup and operation, the QuickPanel
status LED indicator displays as follows:
Chapter 4
Aug 2020
+
45