Emerson Liebert iCOM Training And Service Manual page 60

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

If the end user enables the parameter "Start all Standby units by HT" all available
standby units will turn ON and will continue to run until the return air temperature
in the unit in alarm decrease to approximately 5°F below the high temperature
alarm setpoint.
Example A: In a basic 4 unit configuration, units 1, 2 and 3 are programmed to be
operating and unit 4 is programmed to be standby. The "Rotate By" parameter is
programmed to 1 unit. When the control calls for the units to rotate by "1 unit" the
following sequence occurs:
Unit
Initial Setup
Number
1
Operating
2
Operating
3
Operating
4
Standby
In this configuration, by the fourth rotation the units are back to the original setup -
units 1, 2 and 3 operating with unit 4 in standby.
Example B: In a basic 4 unit configuration, units 1 and 2 are programmed to be
operating and units 3 and 4 are programmed to be standby. The "Rotate By"
parameter is programmed to 2 units. When the control calls for the units to rotate
by "2 units" the following sequence occurs:
Unit
Initial Setup
Number
1
Operating
2
Operating
3
Standby
4
Standby
In this configuration, by every second rotation the units are back to the original
setup - units 1 and 2 operating with units 3 and 4 in standby.
iCOM
Control Training and Service Manual
st
nd
1
2
Rotation
Rotation
Standby
Operating
Operating
Standby
Operating
Operating
Operating
Operating
st
nd
1
2
Rotation
Rotation
Standby
Operating
Standby
Operating
Operating
Standby
Operating
Standby
59
rd
th
3
4
Rotation
Rotation
Operating
Operating
Operating
Operating
Standby
Operating
Operating
Standby
rd
th
3
4
Rotation
Rotation
Standby
Operating
Standby
Operating
Operating
Standby
Operating
Standby