iCOM
Controls Training and Service Manual
Set Alarm Parameters, page 1 of 7
Parameter
Menu
SMALL DISPLAY
line
(Large Display)
S201
(Password)
RTN SNSR
S202
(Return Sensor Alarms)
HI TEMP (High Return
S203
Temperature)
LO TEMP (Low Return
S204
Temperature)
HI HUM
S205
(High Return Humidity)
LOW HUM
S206
(Low Return Humidity)
SENSOR A
S207
(Sensor A Alarms)
HI TEMPA (High
S208
Temperature Sensor A)
LO TEMPA (Low
S209
Temperature Sensor A)
HI HUM A
S210
(High Humid Sensor A)
LO HUM A
S211
(Low Humid Sensor A)
SERVICE MENU's Continued
Default
-
YES
(Enabled)
80°F
65°F
60%
40%
NO
(Disable)
90°F
55°F
70%
30%
96
Shared
Range
in TW1
-
YES, NO
(Enable, Disable)
34 – 210°F
34 – 210°F
1 – 99%
1 – 99%
NO, YES
(Enable, Disable)
34 – 210°F
34 – 210°F
1 – 99%
1 – 99%
Control
Board
Safe
-
-
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF
Yes
CSF