Emerson Liebert iCOM Training And Service Manual page 104

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Set Alarm Parameters, page 6 of 7
Parameter
Menu
SMALL DISPLAY
Line
(Large Display)
S262
(Password)
CI1
S264
(Customer Input 1)
CI2
S265
(Customer Input 2)
CI3
S266
(Customer Input 3)
CI4
S267
(Customer Input 4)
CS
S268
(Call Service)
HTD
S269
(High
Temperature)
LB1
S270
(Loss of Air
Blower 1)
RL
S271
(Reheat Lockout)
HL
S272
(Humidifier
Lockout)
FCL
S273
(FC Lockout)
CL
S274
(Compressor(s)
Lockout)
iCOM
SERVICE MENU's Continued
Default /
Range in
Seconds
-
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
5 sec /
0 – 9999
103
Control Training and Service Manual
Default /
Default /
Range
Range
-
-
YES, NO
Alarm /
(Enable,
Warning,
Disable)
Message
YES, NO
Alarm /
(Enable,
Warning,
Disable)
Message
YES, NO
Alarm /
(Enable,
Warning,
Disable)
Message
YES, NO
Alarm /
(Enable,
Warning,
Disable)
Message
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
YES, NO
Message
(Enable,
/ Alarm,
Disable)
Warning
Control
Board
Safe
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF

Hide quick links: