Options Setup Parameters, page 1 of 2
Menu
SMALL DISPLAY
Line
(Large Display)
S401
(Password)
S402
COMP SEQ (Compressor Sequence)
S403
LP DELAY (Low Pressure Alarm Delay)
S404
LP1 ACT (Actual LP1 Pressure)
S405
LP2 ACT (Actual LP2 Pressure)
S406
EL HEAT (Electric Stages)
S407
HW HEAT (Hot Water Heat On/Off)
S408
ALL HEAT (Total Heat Stages)
S409
LWDconn (LWD Connected)
S410
3P RUN (3P Actuator Runtime)
S411
3P DIR (3P Actuator Direction)
iCOM
SERVICE MENU's Continued
Parameter
109
Control Training and Service Manual
Default
Range
-
-
Auto
Auto, 1, 2
3 min
0 – 5 min
-
14.5 – 87.0 psi
-
14.5 – 87.0 psi
-
0, 1, 2, 3
No
No, Yes
0
0, 1, 2, 3
No
No, Yes
165 sec
30 – 500 sec
DIR, REV
DIR
(Direct,
(Direct)
Reverse)
Control
Board
Safe
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF