Factory Settings Parameters - Emerson Liebert iCOM Training And Service Manual

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

* Notes: Menu lines A008 and A009 are for the unit code. When the status
indicates "Code Not Available" you will need to enter the correct code for the
system as listed on the decal located on the dead front panel of the unit. These
values must be entered on menu lines A003, A005 and A007.
When the unit code has been entered scroll to menu line A008, select the
"Save+Execute command and then select the "Load+Execute" command. The
unit code status menu line A009 should display "OK".
See unit configuration tables in this manual for the various code descriptions
Menu line A011 is for the exception list. If this line displays "Not Available" scroll
to menu line A010, exception list control, and select the "Load" command.
Factory Settings Parameters, page 2 of 9
Menu
SMALL DISPLAY
Line
(Large Display)
A101
(Password)
A102
REFRIG (Refrigerant Type)
A103
MOTOR OL (Main Fan Overload)
A104
AIR LOSS (Loss of Airflow)
A105
# COMP (Number of Compressors)
COMP DLY (Compressor Delay
A106
Time)
COMP ON (Compressor Min ON
A107
Time)
COMP OFF (Compressor Min OFF
A108
Time)
A109
PUMPDOWN (PumpDown)
A110
CAP TYPE (Capacity Control Type)
FLOCT (Loss Of Flow Compressor
A111
Timer)
iCOM
ADVANCED MENU Continued
Parameter
113
Control Training and Service Manual
Default
Range
-
-
R22
R22, R407C
Shutdown,
Shutdown
Disable
Shutdown,
Shutdown
Disable
2
0, 1, 2
0 sec
0 – 120 sec
3 min
0 – 5 min
3 mMin
0 – 5 min
Yes
No, Yes
No, 4step,
HGBP, Digital,
4step
Digital + TH,
SC - HGBP
0 – 180
0 sec
seconds
Control
Board
Safe
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF