Power Supply - B&R Power Panel T80 User Manual

Table of Contents

Advertisement

Device description

4.7.3 Power supply

Danger!
This device is only permitted to be supplied with protective extra-low voltage (PELV).
Protective earth (grounding clip on the device) and the GND connection of the power supply are con-
nected internally in the Power Panel.
The pinout for the power supply is listed in the following table and printed on the back of the Power Panel. The
Power Panel has reverse polarity protection that prevents the supply voltage from being connected incorrectly and
damaging the device.
Terminal
1
2
Required accessories
0TB6102.2010-01
0TB6102.2110-01
The supply voltage is protected internally by a soldered fuse (see technical data) against overload. The device
must be sent to B&R for repairs if the fuse is destroyed in the event of error (fuse replacement).
28
Assignment
+
Accessory terminal block, 2-pin (3.81), screw clamp terminal block 1.5 mm²
Accessory terminal block, 2-pin (3.81), cage clamp terminal block 1.5 mm²
Back
Front (touch screen)
Explanation
24 VDC
GND
Power Panel T80 User's manual V1.03

Advertisement

Table of Contents
loading

Table of Contents