International and national certifications
Toppling / Transport (packaged)
Testing performed per stan-
dard:
EN 60068-2-31
Toppling
Transport (packaged)

10.2.5 Electrical safety

Overvoltage category
Requirement per standard: EN 61131-2
Overvoltage category II
Pollution degree
Requirement per standard: EN 61131-2
Pollution degree 2
Protection rating provided by enclosure (IP code)
Requirement per standard:
Explanation of code num-
EN 61131-2
bers
per standard: EN 60529
Back: ≥IP20
Requirement per
Explanation of code num-
manufacturer
bers
per standard: EN 60529
Front: IP55
118
Requirements per standard:
EN 60721-3-2 / Class 2M1
Weight
Required
<20 kg
Yes
20 to 100 kg
-
>100 kg
-
Topple on all edges
Explanation per standard: EN 60664-1
Equipment of "Overvoltage category II" is energy-consuming equipment to be supplied by the fixed in-
stallation.
Explanation per standard: EN 60664-1
Only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by con-
densation is to be expected.
Meaning for the
protection of equipment
First number
Protected against solid foreign bodies with a
IP2x
diameter ≥12.5 mm
Second number
Not protected.
IPx0
Meaning for the
protection of equipment
First number
Protected against dust.
IP 5x
Second number
Protected against water jets.
IP x5
Requirements per standard:
EN 60721-3-2 / Class 2M2
Weight
Required
<20 kg
Yes
20 to 100 kg
Yes
>100 kg
-
Topple on all edges
Meaning for the
protection of personnel
Protected against touching dangerous parts
with fingers
-
Meaning for the
protection of personnel
Protected against touching dangerous parts
with conductor.
-
Requirements per standard:
EN 60721-3-2 / Class 2M3
Weight
Required
<20 kg
Yes
20 to 100 kg
Yes
>100 kg
Yes
Topple on all edges