B&R Power Panel T80 User Manual page 115

Table of Contents

Advertisement

Surge voltages (Surge)
Testing performed per standard:
EN 61000-4-5
AC mains inputs/outputs
Line / line
AC mains inputs/outputs
Line / ground
DC mains inputs/outputs
Line / line
DC power inputs
Line / ground
DC power outputs
Line / ground
Signal connections, unshielded
Line / ground
All shielded cables
Line / ground
1)
Only for connections with a permitted line length greater than 30 m.
Conducted disturbances
Testing performed per standard:
EN 61000-4-6
AC mains inputs/outputs
DC mains inputs/outputs
Other I/Os and interfaces
1)
Only for connections with a permitted line length greater than 3 m.
Magnetic fields with electrical frequencies
Testing performed per standard:
EN 61000-4-8
Housing, completely wired
1)
Mains frequency per manufacturer data
Voltage dips
Testing performed per standard:
EN 61000-4-11
AC power inputs
1)
Mains frequency per manufacturer data
Short-term interruptions
Testing performed per standard:
EN 61000-4-11 / EN 61000-4-29
AC power inputs
DC power inputs
1)
Mains frequency per manufacturer data
2)
Use of a B&R power supply guarantees that these requirements are met.
Power Panel T80 User's manual V1.03
Requirements per standard:
EN 61131-2 / Zone B
±0.5 kV
1)
Criteria B
±0.5 kV
1)
Criteria B
±0.5 kV
1)
Criteria B
±1 kV
1)
Criteria B
Requirements per standard:
EN 61131-2 / Zone B
150 kHz to 80 MHz
150 kHz to 80 MHz
150 kHz to 80 MHz
Requirements per standard:
EN 61131-2 / Zone B
Requirements per standard:
EN 61131-2 / Zone B
0% residual voltage
250/300 periods (50/60 Hz)
40% residual voltage
10/12 periods (50/60 Hz)
70% residual voltage
25/30 periods (50/60 Hz)
Requirements per standard:
EN 61131-2 / Zone B
0% residual voltage
0.5 periods (50/60 Hz)
1)
20 attempts
Criteria A
0% residual voltage
≥10 ms (PS2)
2)
20 attempts
Criteria A
International and national certifications
Requirements per standard:
EN 61000-6-2
±1 kV
Criteria B
±2 kV
Criteria B
±0.5 kV
Criteria B
±0.5 kV
Criteria B
±0.5 kV
Criteria B
±1 kV
1)
Criteria B
Requirements per standard:
EN 61000-6-2
10 V
80% AM (1 kHz)
Criteria A
10 V
80% AM (1 kHz)
Criteria A
10 V
1)
80% AM (1 kHz)
Criteria A
Requirements per standard:
EN 61000-6-2
30 A/m
3 axes (x, y, z)
50/60 Hz
1)
Criteria A
Requirements per standard:
EN 61000-6-2
1)
20 attempts
Criteria C
1)
20 attempts
Criteria C
1)
20 attempts
Criteria C
Requirements per standard:
EN 61000-6-2
0% residual voltage
1 period (50/60 Hz)
3 attempts
Criteria B
-
1)
-
115