1. Open the shut-off valve for the test connection
2. Via the test connection of the shutoff valve
lower range value to the pressure transmitter.
3. Ensure that the lower range value corresponds to the desired value. Otherwise, correct the
value.
4. Close the shut-off valve for the test connection
5. Open the shut-off valve
6. Open the shut-off valve for the process
8.5.1.2
Commissioning with steam or liquid
Requirement
All valves are closed.
Procedure
①
②
③
④
⑤
⑥
⑦
⑧
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
⑥
at the pressure tapping point.
Pressure transmitter
Shut-off valve
Shut-off valve to process
Shut-off valve for test connection or for bleed screw
Pressure line
Shut-off valve
Drain valve
Compensation vessel (steam only)
④
.
②
, apply the pressure corresponding to the
④
.
③
.
Commissioning
8.5 Application examples
93