5.4 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge
5. Open the shut-off valve
6. Open the shut-off valve for the process
5.4.2

Commissioning with steam or liquid

Requirement
All valves are closed.
Procedure
To commission the pressure transmitter for steam or liquid, proceed as follows:
1. Open the shut-off valve for the test connection
2. Via the test connection of the shut-off valve
start of scale value to the pressure transmitter.
3. Ensure that the lower range value corresponds to the desired value. Otherwise, correct the
value.
4. Close the shut-off valve for the test connection
SITRANS P320/P420 (mA/HART)
Compact Operating Instructions, 06/2018, A5E38874562-AA
at the pressure tapping point.
Pressure transmitter
Shut-off valve
Shut-off valve to process
Shut-off valve for test connection or for bleed screw
Pressure line
Shut-off valve
Drain valve
Compensation vessel (steam only)
.
.
, apply the pressure corresponding to the
.
Commissioning
pressure series
41