Undetected failure in devices with functional safety
Note the following:
● For the maximum current output signal to be output, set the measuring range within the
● Note that a saturation limit > 21.5 mA increases the risk of undetected failures. (Page 162)
● When you configure your process control system, the analog input must distinguish
9.2.13
SV selection [15]
Sets a measured value as a secondary variable (SV).
Setting range:
Factory setting:
9.2.14

Units [16]

Introduction
Depending on the application of the device that you have selected using the "Application"
parameter, you have the option of selecting a unit:
● Level
● Volume
● Volume flow
● Mass flow
The selected unit is displayed in the measurement view.
Use the remote operation to set the associated unit for the "Customized characteristic curve"
application.
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
WARNING
maximum permissible measuring span. You can find the maximum permissible measuring
span of your measuring cell in the section Technical data (Page 199).
between the measured value at saturation (current is ≤ 21.5 mA) and high fault current
(current is ≥ 22.0 mA).
TEMP
ETEMP
LEVEL
VOL
VFLOW
USER
MFLOW
As specified in order
9.2 Parameter assignment over device with display
Sensor temperature
Electronics temperature
Level
Volume
Volume flow
Custom
Mass flow
Parameter assignment