Commissioning
8.5 Application examples
1. Open the shut-off valve for the test connection
2. Via the test connection of the shutoff valve
lower range value to the pressure transmitter.
3. Ensure that the lower range value corresponds to the desired value. Otherwise, correct the
value.
4. Close the shut-off valve for the test connection
5. Open the shut-off valve
6. Open the shut-off valve for the process
8.5.2

Differential pressure and flow rate

8.5.2.1

Commissioning in gaseous environments

Requirement
All shut-off valves are closed.
94
, apply the pressure corresponding to the
at the pressure tapping point.
.
.
.
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC