Absolute Pressure With Front-Flush Diaphragm - Siemens SITRANS P Operating Instructions Manual

Pressure transmitter
Hide thumbs Also See for SITRANS P:
Table of Contents

Advertisement

Technical data
13.2 Measuring accuracy of SITRANS P320
Step response time T
(without electrical damping) - absolute pressure from gauge and differential pressure series
63
Gauge pressure series
All measuring cells
Differential pressure series
250 mbar/25 kPa/3.6 psi
1300 mbar a/130 kPa a/18.8 psi a
5 bar a/500 kPa a/72.5 psi a
30 bar a/3000 kPa a/435 psi a
100 bar a/10 MPa a/1450.3 psi a
Effect of mounting position - absolute pressure from gauge and differential pressure series
In pressure per change of angle
● For absolute pressure (from the gauge pressure series): ≤ 0.05 mbar/0.005 kPa/
0.000725 psi per 10° incline
● For absolute pressure (from the differential pressure series): 0.7 mbar/0.07 kPa/
0.001015 psi per 10° incline
(zero-point correction is possible using the zero point adjustment)
13.2.6

Absolute pressure with front-flush diaphragm

Conformity error at limit point setting, including hysteresis and repeatability
Measuring span ratio r (spread, Turn-Down)
Linear characteristic curve
All measuring cells
Effect of ambient temperature
In percent per 28 °C (50 °F)
All measuring cells
Long-term stability at ±30 °C (±54 °F)
All measuring cells
Step response time T
(without electrical damping)
63
Approx. 0.105 s
212
Approx. 0.105 s
Approx. 0.195 s
Approx. 0.145 s
r = max. measuring span/set measuring span and nominal
measuring range
r ≤ 10
≤ 0.2%
≤ (0.16 • r + 0.24)
In 5 years ≤ (0.25 • r)%
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
10 < r ≤ 30
≤ 0.4%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans p320Sitrans p420

Table of Contents