Rotating The Enclosure - Siemens SITRANS P Operating Instructions Manual

Pressure transmitter
Hide thumbs Also See for SITRANS P:
Table of Contents

Advertisement

5.7

Rotating the enclosure

Introduction
To make the device easier to operate in any mounting position, you have the option of adjusting
the position of the enclosure within a range of 360°.
One retaining screw
for the stainless steel enclosure prevent that the flat ribbon cable is damaged while rotating the
enclosure.
The flat ribbon cable connects the sensor to the electronics.
The tightening torques of the retaining screws are different for the aluminum enclosure and the
stainless steel enclosure. For the tightening torques of the retaining screws, refer to section
Torques (Page 238).
Requirement
You have a 2.5 mm Allen key.
Rotating the aluminum enclosure
1. Loosen the retaining screw
2. Rotate the enclosure to the desired position (but no further than the end stop).
3. Tighten the retaining screw.
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
Retaining screw
for the aluminum enclosure and two retaining screws (front and back)
by half a rotation.
Installing/mounting
5.7 Rotating the enclosure
63