Diagnostics and troubleshooting

12.2 Diagnostic messages

12.2
Diagnostic messages
The following table shows the IDs of diagnostic messages and possible causes and
instructions for corrective actions.
ID
Symbols
Message
A0
Event counter 1
Number overruns above
threshold
Maintenance alarm
A1
Event counter 1
Number underruns above
threshold
Process value alarm
A2
Event counter 1
Number underruns above
threshold
Maintenance required
A3
Event counter 1
Number underruns above
threshold
Maintenance alarm
A4
Event counter 2
Number overruns above
threshold
Process value alarm
A6
Event counter 2
Number overruns above
threshold
Maintenance required
A7
Event counter 2
Number overruns above
threshold
Maintenance alarm
A8
Event counter 2
Number underruns above
threshold
Process value alarm
192
Cause/Remedy
The number of overruns of the process value (set in parameters
"Upper limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of underruns of the process value (set in parameters
"Lower limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of underruns of the process value (set in parameters
"Lower limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of underruns of the process value (set in parameters
"Lower limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of overruns of the process value (set in parameters
"Upper limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of overruns of the process value (set in parameters
"Upper limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of overruns of the process value (set in parameters
"Upper limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of underruns of the process value (set in parameters
"Lower limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
Operating Instructions, 11/2019, A5E44852162-AC