Commissioning
8.5 Application examples
9. Partially open the differential pressure valve
10.Close the differential pressure valve.
11.Close the vent valve (sealing plug with vent valve) on the negative side of the pressure
transmitter.
12.Open the differential pressure valve
13.For a lower range value of 0 bar, check the zero point (4 mA) and correct the lower range
value if it is different.
14.Close the stabilizing valve
15.Open the differential pressure valves (
8.5.2.3

Commissioning with vapor

Requirement
All valves are closed.
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
valve
● Follow the specified procedure for commissioning.
Hot vapor
Danger of injury.
You can briefly open the drain valves
● Only open the drain valves
98
WARNING
and the differential pressure valve
is then opened, the pressure transmitter
WARNING
until liquid escapes without bubbles.
with half a revolution.
.
and
) completely.
to clean the line. Hot vapor can escape in the process.
briefly, and close them again before vapor escapes.
Operating Instructions, 11/2019, A5E44852162-AC
are both open and the stabilizing
can be damaged by the flow of vapor.
SITRANS P320/P420 with 4 to 20 mA/HART