Upper Fault Current [12]; Lower Saturation Limit [13] - Siemens SITRANS P Operating Instructions Manual

Pressure transmitter
Hide thumbs Also See for SITRANS P:
Table of Contents

Advertisement

3.55 mA
9.2.10

Upper fault current [12]

Adjusts the magnitude of the upper fault current
Setting range:
Factory setting:
3.55 mA
9.2.11

Lower saturation limit [13]

Sets the lower threshold for the lower saturation limit
The loop current cannot drop below the set threshold.
Setting range:
Factory setting:
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
3.8 mA
4 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
Between upper saturation limit
22.8 mA, or as specified in order
3.8 mA
4 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
Between lower fault current
3.8 mA, or as specified in order
9.2 Parameter assignment over device with display
20 mA
.
und 22.8 mA
20 mA
.
and 4 mA
Parameter assignment
20.5 mA
22.8 mA
20.5 mA
22.8 mA
125