Siemens SITRANS P DS III Operating Instructions Manual

Siemens SITRANS P DS III Operating Instructions Manual

Digital pressure transmitter
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS P DS III

  • Page 3 ___________________ SITRANS P DS III/P410 with Introduction PROFIBUS PA ___________________ Safety information ___________________ SITRANS Description ___________________ Installing / mounting Pressure transmitter SITRANS P DS III/P410 with ___________________ PROFIBUS PA Connecting up ___________________ Operation Operating Instructions ___________________ Operator control functions via PROFIBUS...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Electrostatic-sensitive devices ....................19 Description ............................21 System configuration ......................21 Application ..........................22 SITRANS P DS III and SITRANS P410 .................. 24 Structure ..........................24 Nameplate layout ........................26 Measuring point label layout ....................27 Principle of operation ......................27 3.7.1...
  • Page 6 Units display ........................... 74 6.4.3 Error display ........................... 74 6.4.4 Mode display .......................... 75 6.4.5 Status display ......................... 76 Local operation........................76 6.5.1 Control elements for local operation ..................76 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 7 Calibration interval and service interval ................120 7.9.3 Clearing warning ........................121 7.9.4 Clearing the alarm ......................... 121 7.9.5 Min/max indicator ........................122 7.10 Simulation ..........................122 7.10.1 Overview of simulation ......................122 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 8 Check write protection with SIMATIC PDM ................. 158 8.7.7.4 Speeding up the commissioning process ................159 8.7.7.5 Resetting the device ......................159 8.7.8 Quit PROFIsafe commissioning ................... 160 8.7.8.1 Preparations for maintenance and service ................160 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 9 Interrupts, error and system alarms ..................... 189 12.1 Overview of status codes ...................... 189 12.2 Errors ............................ 192 Technical data ............................ 193 13.1 Overview of technical data ....................193 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 10 SITRANS P, DS III/P410 for gauge pressure and absolute pressure from the gauge pressure series........................229 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series ..................... 231 14.3 SITRANS P DS III/P410 for level ..................234 14.4...
  • Page 11: Introduction

    The programming manual is an integral part of the CD, which is either supplied or can be ordered. The programming manual is also available on the Siemens homepage. On the CD, you will also find the catalog extract with the ordering data, the Software Device Install for SIMATIC PDM for additional installation, and the required software.
  • Page 12: Scope Of The Instructions

    WARNING Using a damaged or incomplete device Danger of explosion in hazardous areas. • Do not use damaged or incomplete devices. See also Return procedure (Page 187) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 13: Transportation And Storage

    The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
  • Page 14 Introduction 1.7 Notes on warranty SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 15: Safety Information

    Pressure Equipment Di- Directive of the European Parliament and of the Council on the rective PED approximation of the laws of the Member States concerning 97/23/EC pressure equipment. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 16: Improper Device Modifications

    Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note...
  • Page 17: Use In Hazardous Areas

    • Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit. • Observe the specifications for the electrical data on the certificate and/or in Chapter "Technical data (Page 193)". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 18: Use Of Incorrect Device Parts In Potentially Explosive Environments

    The key cover may be opened temporarily at any time for the purposes of operating the pressure transmitter, even during plant operation; the screws should then be tightened again. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 19: Electrostatic-Sensitive Devices

    • Devices and tools used must be free of static charge. • Hold modules only by their edges. • Do not touch connector pins or conductor tracks on a module with the ESD notice. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 20 Safety information 2.4 Use in hazardous areas SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 21: Description

    The maintenance station assists the maintenance engineer in guaranteeing high plant availability, securing this long-term using optimization measures, and implementing the maintenance measures using a minimum of personnel, materials, energy, expenses, etc. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 22: Application

    Depending on the device version, you can use the pressure transmitter for the following types of measurement: ● Gauge pressure ● Absolute pressure ● Differential pressure SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 23 ● Differential pressure ● Gauge pressure, suitable for small positive or negative pressure value ● In combination with a primary element: flow rate q ~ SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 24: Sitrans P Ds Iii And Sitrans P410

    These instructions describe the pressure transmitters SITRANS P DS III and SITRANS P410. The main difference of the SITRANS P410 is the higher measuring precision compared to the SITRANS P DS III. Refer to the information in the section Technical data (Page 193).
  • Page 25 ● On the upper face of the enclosure you can see crosshead screws which secure the key ① cover , under which there are 3 keys for local operation. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 26: Nameplate Layout

    On the opposite side is the nameplate with approval information. This nameplate shows the firmware and hardware versions, for example. You must also observe the information in the relevant certificate for a pressure transmitter version for use in hazardous areas. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 27: Measuring Point Label Layout

    This chapter describes how the pressure transmitter works. First the electronics are described, and then the physical principle of the sensors which are used with the various device versions for the individual measurement types. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 28: Operation Of The Electronics

    ● The digital signal is analyzed in a microcontroller and corrected with regard to linearity and thermal characteristics. ⑦ ● The signal is available at an electrically isolated PA interface on the PROFIBUS PA. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 29: Principle Of Operation Of The Measuring Cell

    ● Gauge pressure ● Absolute pressure ● Differential pressure and flow rate ● Level The following process connections are available, for example: ● G1/2 B, 1/2-14 NPT ● Male thread: M20 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 30: Measuring Cell For Gauge Pressure

    Pressure transmitters with spans ≤ 6.3 MPa measure the inlet pressure against atmosphere, those with spans ≥ 16 MPa the inlet pressure against vacuum. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 31: Measuring Cell For Differential Pressure And Flow Rate

    (bridge circuit) of the differential pressure sensor. ● The change in the resistance causes a bridge output voltage proportional to the differential pressure. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 32: Measuring Cell For Level

    The displacement changes the resistance of the four doped piezoresistors in the bridge circuit. ● The change in the resistance causes a bridge output voltage proportional to the differential pressure. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 33: Measuring Cell For Absolute Pressure From The Differential Pressure Series

    (bridge circuit) of the absolute pressure sensor. ● The change in the resistance causes a bridge output voltage proportional to the absolute pressure. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 34: Measuring Cell For Absolute Pressure From The Gauge Pressure Series

    The inlet pressure (p ) is transferred to the gauge pressure sensor via the seal diaphragm ④ ⑤ and the filling liquid , displacing its measuring diaphragm. The displacement changes SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 35: Measuring Cell For Absolute Pressure, Front-Flush Membrane

    (bridge circuit) of the absolute pressure sensor. The change in the resistance causes a bridge output voltage proportional to the inlet pressure. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 36: Remote Seal

    SIMATIC PDM offers simple monitoring of process values, alarms, and device status information. SIMATIC PDM allows the process device data to be: ● displayed ● set ● modified ● saved ● diagnosed ● checked for plausibility SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 37: Profibus

    PROFIBUS DP via coupler units. This is also connected to the process control system. Both bus systems use the same protocol layer. This makes PROFIBUS PA a "communications-compatible" extension of the PROFIBUS DP into the field. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 38: Properties

    Properties PROFIBUS PA allows bidirectional communication between a bus master and field devices. At the same time, the shielded two-strand wiring provides auxiliary power to the two-wire field devices. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 39: Installing / Mounting

    Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 40 • In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national regulations and the requirements stated in the relevant approvals. See also Technical data (Page 193) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 41 Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed. • Close the device as described in Chapter "PROFIBUS assembly guidelines (Page 66)". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 42 Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. • Prevent severe external stresses and loads from acting on the device. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 43: Installation Location Requirements

    • Make sure that process connectors are clean, and suitable gaskets and glands are used. • Mount the device using suitable tools. Refer to the information in Technical data (Page 193) for installation torque requirements. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 44: Disassembly

    • If the device contains dangerous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. • Secure the remaining connections so that no damage can result if the process is started unintentionally. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 45: Installation (Except Level)

    Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensate produced can drain in the main line and thereby avoid corruption of the measured values. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 46: Installation (Except Level)

    ● On a wall or a mounting frame using two screws ● On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket Fasten the pressure transmitter mounting bracket using the two screws provided. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 47 Fastening the pressure transmitter on the mounting bracket Image 4-2 An example of fastening the pressure transmitter on the mounting bracket in the case of differential pressure and horizontal differential pressure lines SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 48: Level" Installation

    Instructions for level installation Requirements Note Compare the desired operating data with the data on the nameplate. Please also refer to the information on the remote seal if this is fitted. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 49: Installation For Level

    2. Screw on the pressure transmitter's flange. 3. Observe the installation position. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 50: Connection Of The Negative Pressure Line

    Measurement assembly on an open container Lower filling level Δp Start of scale value Upper filling level Δp Full-scale value Pressure ρ Density of the measured medium in the container Acceleration due to gravity SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 51 Lower filling level Δp Start of scale value Upper filling level Δp Full-scale value Pressure ρ Density of the measured medium in the container Acceleration due to gravity SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 52 The process connection on the negative side is a female thread -18 NPT or an oval flange. Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 53: Remote Seal Installation

    The pressure rating specified on the remote seal applies to reference conditions according to IEC 60770. • For the maximum permissible pressure at higher temperatures, please refer to the standard specified on the remote seal. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 54: Installation Of The Remote Seal With The Capillary Line

    – If halocarbon oil is used as a fill fluid, this maximum height difference is only H 1max. 4 m; see installation type A and installation type B. If negative overpressure is observed during measurements, reduce the permissible height difference accordingly. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 55 Distance between the container flange and the pressure transmitter For absolute pressure measurements (vacuum), install the measuring device at least at the height of the remote seal or below it (see installation types C). SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 56 Full scale pressure ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Distance between the container flange and the pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 57 Full-scale value Start of scale pressure start Full scale pressure ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Gland distance SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 58 Density of the process medium in the container ρ Density of the filling oil in the capillary line of the remote seal Acceleration due to gravity Lower filling level Upper filling level Gland distance SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 59 * g * H - ρ * g * H Full-scale value: = ρ * g * H - ρ * g * H Between the measuring points, no vacuum SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 60: Turing The Measuring Cell Against Housing

    The turning range for pressure transmitters for differential pressure and flow rate, absolute pressure from the differential pressure series and level is identified in a similar manner. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 61: Rotating The Display

    You can turn it by ±90° or ±180°. 3. Screw the covers back on as far as they will go. 4. Secure the covers with the cover catch. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 62 Installing / mounting 4.7 Rotating the display SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 63: Connecting Up

    • Connect the device in accordance with the specified power supply and signal circuits. The relevant specifications can be found in the certificates, in Chapter "Technical data (Page 193)" or on the nameplate. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 64 • Circuits of limited energy may also be connected in the energized state in hazardous areas. • Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the relevant certificate SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 65: Incorrect Measured Values With Incorrect Grounding

    For metal housings there is an increased electromagnetic compatibility compared to high- frequency radiation. This protection can be increased by grounding the housing, see Chapter "PROFIBUS assembly guidelines (Page 66)". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 66: Connecting The Device

    TERMINALS" is provided at the side of the housing. Procedure ② 1. Insert the connecting cable through the cable gland ⑥ 2. Connect the device to the plant with the protective conductor connection SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 67 Closing the device ④⑦ 1. Screw the covers back on as far as they will go. ③⑥ 2. Secure each cover with the cover catch ① 3. Close the key cover SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 68: Connecting The M12 Connector

    A conductive connection must not exist between the shield and the connector housing. WARNING The connector may only be used for Ex ia devices and non-Ex devices; otherwise the safety required for the approval is not guaranteed. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 69 Image 5-3 Preparing the connecting cable ① ③ Reference edge for stripping Insulating sleeve over the shield ② ④ Reference edge for the dimension Shrink sleeve specifications for cable assembly SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 70 Layout for M12 jack Layout for M12 connector ① ① M12 x 1 thread Positioning slot ② Positioning catch Not connected Not connected Shield Shield Middle jack contact not connected SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 71: Operation

    Key lock and write protection Measured value display Unit Bus address Device mode Decimal point Zero point drift LO calibration HI calibration Customized characteristic curve Diagnostics function Measurement type SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 72: Basic Safety Instructions

    The operating instructions in the section "Local operation (Page 76)" apply if the device has been delivered with a dummy cover. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 73: Display

    Violation of upper limit displays are also referred to as status since they have meanings dependent on the settings. ⑧ If the communication display blinks, this indicates an active communication. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 74: Units Display

    "Error" appears in the measured value display. A status code indicating the type of error appears in the bottom line of the display. This diagnostic information is also available via PROFIBUS. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 75: Mode Display

    The selected active mode is shown in the mode display. Display Image 6-4 Example for mode display In the example, a damping of 0.2 seconds was set in mode 4. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 76: Status Display

    The pressure transmitter can be operated on-site using the keys. You can select and execute the functions described in the table using adjustable modes. Operation by buttons is not available for devices without display. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 77 Local operation is possible if you are in measuring mode and neither "L", "LA" nor "LL" is output in the mode display. If operations are disabled, parameters can still be read. An error message is output if you try to change parameters. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 78 Display of current measuring range LO calibration Increase Decrease Apply Calibrate bottom point of characteristic value value HI calibration Increase Decrease Apply Calibrate top point of characteristic value value SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 79: Operation Using Buttons

    0 and 100 seconds using the increments of 0.1 seconds. This electrical damping also has an effect on the built-in basic damping of the device. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 80: Calibrate Zero Point

    Calibrate zero point Introduction A zero point calibration is used to correct zero errors resulting from the mounting position of the transmitter. You must proceed differently depending on the device version. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 81: Locking Of Buttons And Functions

    To lock the buttons, proceed as follows: 1. Set mode 10. 2. Activate the locking of buttons and functions. 3. Save with the [M] button. "L" is output in the mode display. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 82: Measured Value Display

    ● Volume Procedure To select the source for the measured value display, proceed as follows: 1. Set mode 13. 2. Select the variable. 3. Save with the [M] button. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 83 Flow not relevant for relative and ab- solute pressure *) The option of selecting the physical unit is additionally determined by the channel setting (mass or volume) of the analog input and totalizer function blocks. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 84: Unit

    In mode 14, set the physical unit in which the device's measured value display should be represented. Requirement You have already selected the desired source for the measured value display in mode 13. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 85 HG Table 6- 10 Unit for volume (V) Unit Display Unit Display pint (US) Pint quart (US) Quart US gallon imp. gallon ImGAL bushel BUSHL barrel barrel liquid bblli SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 86 Long tons / m LT/m T / h Long tons / h LT/h T / d Long tons / d LT/d Table 6- 13 Unit for level (L) Unit Display Unit Display SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 87 SIMATIC PDM which does not appear in the corresponding valid list, the current measurement value will be shown without a unit in the measured value display. See also Units of the pressure transducer block (Page 102) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 88: Bus Address

    Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0, with analog input function block, without totalizer Delivery state Profile-compatible with extensions: Full functionality of the SITRANS P with: Analog input function block • Totalizer • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 89 If the device is exchanging period data, no change is possible to the device operating type. Table 6- 18 Device master data file Display File name pa_29700.gsd or pa_39700.gsd siem80A6.gsd sip1804B.gsd [128] pa_29740.gsd or pa_39740.gsd See also Errors (Page 192) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 90: Position Of The Decimal Point

    The zero-point adjustment is shown in mode 18. The zero point adjustment is carried out by the zero point calibration in mode 7 or by the calibration procedure in modes 19 and 20. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 91: Lo Calibration

    The measured value display switches to the current pressure value. Using the [↑] and [↓] keys, you can enter the reference value starting from there. 4. Press the [↑] und [↓] buttons simultaneously for 2 seconds. 5. Save with the [M] button. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 92: Hi Calibration

    Errors (Page 192) Calibrating the sensor (Page 125) 6.5.13 HI calibration Introduction The slope of the characteristic is changed in mode 20. This rotates the characteristic around setting point LO. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 93 20, or the lower reference pressure in mode 19. As long as mode 20 is active, you can repeat this procedure as often as necessary. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 94 The display shows the value of the last calibration procedure, with the appropriate unit. 2. Leave the mode by pressing [M]. See also Errors (Page 192) Calibrating the sensor (Page 125) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 95: Operator Control Functions Via Profibus

    The device functions are subdivided into blocks of different task areas. They can be parameterized during asynchronous data transmission. Pressure Sensor Temperature Image 7-1 Block circuit diagram of collection and processing of measured values SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 96 The output of this block forwards the totalized values and the corresponding status information via PROFIBUS. Local operation and display The display shows the desired measured value with its physical unit. You can select different functions for local operation. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 97 Electronics temperature transducer block Electronics temperature Analog input function block Output Totalizer function block Totalizer output See also Measured value display (Page 82) Cyclical data transfer (Page 165) Acyclic data transfer (Page 170) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 98: Pressure Transducer Block

    SEC 1 Secondary variable 1 Sensor SEC 2 Secondary variable 2 Temperature PRIM Primary variable SEC 3 Secondary variable 3 Image 7-2 Function groups of the pressure transducer block SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 99 By means of a multiplication with the density the volume is used to compute the mass. This is stored in SEC 3. The temperature value of the pressure sensor is available in the "temperature" parameter. See also Acyclic data transfer (Page 170) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 100: Linearization Type Function Group

    No linearization Level: Volume User de- Linearization of container characteris- fined (table) tics. The relationship between level and volume is described using a maximum of 31 nodes at arbitrary intervals. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 101 The device checks which pair of nodes bracket the pressure (secondary variable 1) relative to the measurement range. To convert the pressure to the measured value (primary variable), the device interpolates on a line between the interpolation nodes. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 102: Units Of The Pressure Transducer Block

    Depending on the measurement type, units are allowed from the following measurement functions: Table 7- 5 Overview of available units Variable Measurement type Pressure Level Volume Volume flow Mass flow Raw pressure value Secondary variable 1 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 103: Electronics Temperature Transducer Block

    "UNCERTAIN – Value not accurate – high/low-limit". This procedure is accompanied by a PROFIBUS diagnostic message "Electronics temperature too high". There are also peak indicators for maximum and minimum values available. See also Min/max indicator (Page 122) Status (Page 167) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 104: Analog Input Function Block

    If the measured value has the status "Bad", the shutdown logic can output a safety preset value: This may be the last usable measured value or a preset substitute value. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 105: Totalizer Function Block

    Image 7-6 Function groups of the totalizer function block Incoming measured value from the trans- Manual ducer for pressure Out of Service SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 106: Overview Of Operating Functions

    In measurement mode, measurement values such as pressure, fill level or flow are available on the PROFIBUS-PA interface. PROFIBUS PA communication is signaled by the communication symbol "o" on the display. See also Display elements (Page 73) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 107: Settings

    To select pressure measurement, proceed as follows: 1. Start SIMATIC Manager. 2. Create a device with the desired measurement type. 3. To open SIMATIC PDM, double-click on the device you have created. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 108: Level Measurement

    "working range" > > > Output scaling Unit: as in "working range" Start of scale value: as in "working range" Full scale value: as in "working range" SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 109 ● Create an assignment between the measured volume value and the output value by setting these parameters: > Output > > Function block 1 - analog input Channel: Measured value (primary variable) > > > Measured value scaling SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 110 > Characteristic curve Characteristic curve User-defined table type: > > > Nodes New number of max. 31 nodes: x[n] measurement Pressure value range: y[n] working range: Corresponding volume value SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 111: Flow Measurement

    (with SIMATIC PDM) Output, totalizer output, reset totalizer output Current flow/time, volume or mass that has flowed over a time seg- ment, Dosing SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 112 ● To acquire the current flow, use "Function Block 1 – Analog Input". Create an assignment between the measured flow value and the output value by setting these parameters: > Output > > Function Block 1 - Analog Input SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 113 ● Creep quantity suppression sets the measured flow quantity to 0, when the value falls below the preset limit. Enter the application point as a % of the operating range (volume flow). SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 114: Adjusting To A Desired Process Value

    The following examples illustrate this: Procedure The procedure is shown by means of two concrete application examples. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 115 Analog input function block Input for start-of-scale value: Input for final value: 400.0 Output for start-of-scale value: Output for final value: 2000.0 Unit (output): Text Unit text (output): Barrels SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 116: Electrical Damping (Filter Time Constant)

    Acts like an active keypad block. Changes to SIMATIC PDM blocking and no parameters (except for keypad block) are not enabling of local possible either with local operation or using operation SIMATIC PDM. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 117: Warning And Alarm Limits

    Table 7- 9 Limits and status displays Status Status Violation Display G_137 Low warning limit G_138 High warning limit G_141 Low alarm limit G_142 High alarm limit SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 118 High warning limit Low alarm G_141 Low alarm limit High warning limit G_142 High alarm limit Low warning limit Hysteresis Time Measured value Image 7-8 Warning and alarm limits SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 119: Failure Behavior

    Counting continues with the last input value that U_072 had the "Good" status prior to the failure. Operation The bad measured value is accompanied by the B_0xx status assigned to it by the transducer block. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 120: Diagnostics Functions

    The interval is selectable. The timers can monitor on two levels, first giving a warning, then an alarm. Image 7-9 Calibration and service intervals Timer value Time Interrupt Warning SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 121: Clearing Warning

    To clear an alarm, proceed as follows: 1. Clear the alarm. The diagnostic message is deleted and the status set back to "Good". 2. Perform the calibration or service. 3. Reset the timer. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 122: Min/Max Indicator

    You can generate process values without recording real measured values. The value range of simulated process values can be tested fully: This makes the simulation of errors possible. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 123: Operating Instructions, 02/2016, A5E00053276-08

    5. Transmit the settings from the program into the pressure transmitter. You can observe the behavior of the input in e.g. SIMATIC PDM. To return to normal operation afterwards, you must switch off the simulation. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 124: Simulating The Pressure Sensor

    2. Set the simulation mode and the parameters: – Simulation mode "Fixed" and parameter pressure value – Simulation mode "Ramp" and ramp parameters 3. Transmit the settings from the program into the pressure transmitter. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 125: Simulating Sensor And Electronics Temperature

    If the calibration is smaller than the smallest span, the following status code accompanies the measured value: "Bad, configuration error" In this case, recalibration the lower or the upper sensor trim point with a sufficiently large calibration span. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 126: Correcting For Positional Error

    ● Installation-caused preset pressures, for instance fluid columns in the pressure line to the pressure transmitter ● The screw-mounting on the process plant, e.g. measuring ranges from 1 to 20 mbar (differential pressure), can respond more sensitively to the screw-mounting. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 127: Reset

    "Unsure, initial value, value constant" until a measured value result is available. See also Resetting the PROFIBUS address (Page 128) Device operation type (Page 88) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 128: Warm Start/Restart

    If you remove the pressure transmitter from the PROFIBUS chain, reset its address to 126. This allows you to include the pressure transmitter in this or another system if necessary. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 129: Functional Safety

    Functional safety Safety function The safety function of SITRANS P DS III with PROFIsafe protocol (ordering option -Z C21) is based on the measurement of pressure. The pressure is converted to a digital measured value and transmitted via PROFIsafe communication. Fault tolerance allowances must be made, because the measured value transferred to the automation system by the pressure transmitter can deviate from the physical value.
  • Page 130: Safety Integrity Level (Sil)

    Only one SITRANS P DS III device is required for single-channel operation for SIL 2. Safety Integrity Level (SIL) The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4.
  • Page 131 SIL 3 90 to 99 % SIL 2 SIL 3 SIL 4 > 99 % SIL 3 SIL 4 SIL 4 Operational reliability in accordance with IEC 61511-1, Section 11.4.4 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 132: Settings

    The safety characteristics necessary for using the system are listed in the "SIL Declaration of Conformity". These values apply under the following conditions: ● SITRANS P DS III pressure transmitters are only used in applications with a low demand rate for the safety function (low demand mode).
  • Page 133: Maintenance/Check

    ● Fault rates are calculated on the basis of a mean time to repair (MTTR) of eight hours (order option C21). ● Only one SITRANS P DS III device is required for single-channel operation in accordance with SIL 2. ● Secure data transmission is only guaranteed when using a PROFIsafe master.
  • Page 134: Checking Safety Function/Proof Test

    ● Select the interval according to the process and ambient conditions of the installation location of the pressure transmitter. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 135: Checking Temperature Sensors

    The difference between the first input pressure and the second input pressure is ≥ 10% of the maximum measuring range. Checking the measuring range 1. Apply an initial input pressure. 2. Check the transferred value. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 136 3. Apply an input pressure value that is ≥ 1% of the maximum measuring range below the threshold. ① Threshold Image 8-4 Example of monitoring of a minimum pressure SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 137 ≤ 0.2%. Negative measurement result If the two-point measurements of the pressure transmitter were not successful, the SIL level is no longer guaranteed. ● Replace the pressure transmitter. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 138: Two-Point Measurement ≥ 50% Of The Maximum Measuring Range

    2. Apply an input pressure value that is above the threshold. 3. Apply an input pressure value that is ≥ 1% of the maximum measuring range below the threshold. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 139 ① Threshold Image 8-8 Example of monitoring of a maximum pressure Result The two-point measurements are successful when the deviation between input pressure and transferred value is ≤ 0.2%. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 140: Checking Pressure Transmitter For External Damage

    1. Check the connection between the pressure transmitter and pneumatic block and between the pneumatic block and pipelines in the plant for leaks. 2. Observe the safety information and specifications in chapter Installing / mounting (Page 39). SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 141: Checking A Device With Add-On Remote Seal

    In the following example, you see that PROFIsafe and PROFIBUS devices can be operated simultaneously on a PROFIBUS network. Note PROFIsafe devices can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 142 Functional safety 8.7 PROFIsafe Image 8-9 Example of PROFIsafe communication See also PI PROFIBUS - PROFINET (http://www.profibus.com/home/) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 143: Further Information

    You will find more information on safety engineering and installing PROFIsafe in the document "Safety Engineering in SIMATIC S7". See also General functional safety (http://www.siemens.com/safety) Functional safety in process instrumentation (http://www.siemens.com/SIL) Product information on SITRANS P in the Internet (http://www.siemens.com/sitransp) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 144: Preconditions

    ● Firmware from 301.02.01 8.7.5 PROFIsafe Configuration For safety reasons, the PROFIsafe device ships with default settings. Requirement Before you commission the PROFIsafe device, configure it, for example in STEP 7. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 145: Import Edd With Simatic Pdm

    Procedure 1. You are in the "Catalog" view with the "standard" profile. Go to the device in the catalog: – "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe" valid for firmware 0301.02.01 and 0301.02.02 – "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe V2"...
  • Page 146 – crc length = 2, F-Par-Version = 0 → V1 PROFIsafe protocol 10.Adapt the value of the "F_WD_Time" parameter to the number of PROFIBUS devices connected to the PROFIBUS-PA bus. The default value for this parameter is 1 second. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 147 • "F-I/O passivated": Cyclic redundancy check error/sequence number error. • "F-I/O passivated": F-monitoring time for safety frame exceeded. To make sure that PROFIsafe V2 communication works correctly, use only F-CPUs approved for this purpose. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 148: Configure Cfc

    A selection list of transfer rates is displayed. – Connect the parameter value of the block "F_PA_AI" with the real value of the configured device. 5. Click the "Compile program" button. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 149 Until PROFIsafe commissioning is completed, the device displays the error "B_60: Bad function check". This has no effect on the operation of the device. The error message lets you know that the device is not yet in "S4". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 150: Write Protection

    Activate write protection using PIN in SIMATIC PDM (Page 151) Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Disable write protection using PIN in SIMATIC PDM (Page 160) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 151: Activate Write Protection Using Pin In Simatic Pdm

    Before you commission the PROFIsafe device, configure it, for example in STEP 7. Process Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Commission PROFIsafe with SIMATIC PDM (Page 153) Check write protection with SIMATIC PDM (Page 158) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 152: Activate And Parameterize Profisafe With Simatic Pdm

    The device has activated the PROFIsafe functionality. The relevant menus for PROFIsafe commissioning are active in SIMATIC PDM. Note If you want to change the "F_Dest_ADD" parameter later, reset the device. Resetting the device (Page 159) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 153: Commission Profisafe With Simatic Pdm

    Commission PROFIsafe with SIMATIC PDM Start PROFIsafe commissioning 1. In the "Device" menu, select the "Wizard - PROFIsafe commissioning" command. The "Wizard - PROFIsafe commissioning" dialog box is opened. 2. Click "Next". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 154 Functional safety 8.7 PROFIsafe 3. If the checksums are the same, select the checkbox. You obtain further information. 4. Click "Next". 5. Click "OK" to confirm the message that follows. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 155 Functional safety 8.7 PROFIsafe 6. In the "Device" menu, select the "Wizard - continue PROFIsafe commissioning" command. The "Wizard - PROFIsafe commissioning" dialog box is opened again. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 156 The PROFIsafe commissioning status shows the following: "S2 = application not inspected". 7. If the checksums are still the same, select the checkboxes. The PROFIsafe commissioning status shows the following: "S3 = inspection completed". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 157 The PROFIsafe commissioning status shows the following: "S4 = PROFIsafe operation mode" 9. Click the "Close" button. Result The "Wizard - PROFIsafe commissioning" dialog box is closed. The PROFIsafe device is in "S4" and is write protected accordingly. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 158: Check Write Protection With Simatic Pdm

    The additional write protection by HOST is set in Continuous Function Chart (CFC) in the F_PA_AI function block, I_PAR_EN parameter. Note If you need a user-defined PIN write protection, you will find it in the appropriate chapter. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 159: Speeding Up The Commissioning Process

    8.7.7.5 Resetting the device The following procedure no longer belongs to standard commissioning. Take the following steps only when necessary. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 160: Quit Profisafe Commissioning

    Procedure 1. In the "Device" menu, select the "Write protection" command. 2. Click on the "OFF" button. 3. Enter the user-defined PIN, the default PIN, or the super PIN. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 161: Replacing A Device

    "Process Devices - Network View" of the SIMATIC Manager. 8.7.9.1 Making settings locally Procedure 1. Set mode 16. 2. Set the device mode [129] with the [↑] and [↓] keys. 3. Save with the [M] key. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 162: Configuration With Host System

    [128]: pa_29740.gsd or pa_39740.gsd [129]: SI0180A6.gsd or SIEM80A6.gsd or SI0280A6.gsd 8.7.9.2 Configuration with host system Note Generic Station Description (GSD) The generic station description file in HW Config remains the same: SI0180A6.gsd. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 163 After downloading the data to the device, cyclic communication with the device is once again possible. See also Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Commission PROFIsafe with SIMATIC PDM (Page 153) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 164 Functional safety 8.7 PROFIsafe SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 165: Configuration/Project Engineering

    This allows the optimization of the data quantity to be transmitted. In the Siemens control system, the GSD files of all the usual devices are already available, and they are also available on the Internet and can be imported later.
  • Page 166 Totalizer reset function output output 0 Normal operation of totalizer Integration running. 1 Step integration and reset integrator back to 0. 2 Stop integration and load integrator with preset value. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 167: Transmission Of User Data Over Profibus

    The status provides information on: ● Usability of the measured value in the application program ● Device status, e.g. self-diagnosis or system diagnostic ● Additional process information, for instance process alarms SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 168: Diagnosis

    The diagnostic object consists of four bytes. For the pressure transmitter, only the first two bytes are relevant. Table 9- 5 Diagnostics messages Byte Meaning of "1" Cause Measure Byte 0 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 169 In case of a restart, the device will no longer participate in cyclic user data exchange unless the system configu- ration is changed. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 170: Acyclic Data Transfer

    So that multiple class 2 masters can access the same pressure transmitter at the same time, the device supports up to four C2 connections. However, you must ensure that the same data is not being written. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 171: Commissioning

    5 minutes after the power supply is switched on. When it starts up, the pressure transmitter goes through an initialization routine (display at the end: "Init done"). If the pressure transmitter does not complete the initialization routine, check the auxiliary power. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 172: Gauge Pressure, Absolute Pressure From Differential Pressure Series, And Absolute Pressure From Gauge Pressure Series

    10.3.1 Commissioning for gases Usual arrangement Special arrangement Measuring gases above the pressure tapping Measuring gases below the pressure tapping point point SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 173 5. Close the shut-off valve for the test connection ⑥ 6. Open the shut-off valve at the pressure tapping point. ③ 7. Open the shut-off valve for the process SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 174: Commissioning With Steam Or Liquid

    3. Check the start of scale value. 4. If the start of scale value differs from the value desired, correct it. ④ 5. Close the shut-off valve for the test connection SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 175: Differential Pressure And Flow Rate

    Measure • Make sure the locking screw and/or the vent valve are screwed in and tightened. • Ensure that the valves are operated correctly and properly. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 176: Commissioning In Gaseous Environments

    ② ⑦ Stabilizing valve Blow-out valve ③ ④ ⑧ Differential pressure valves Condensation vessels (optional) ⑤ ⑨ Differential pressure lines Differential pressure transducer Requirement All shut-off valves are closed. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 177: Commissioning For Liquids

    Pressure transmitter above the pressure transducer differential pressure transducer ① Pressure transmitter ⑦ Drain valve ② ⑧ Stabilizing valve Gas collector vessels (optional) ③ ④ ⑨ Differential pressure valves Differential pressure transducer SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 178 12.Check and if required correct the zero point when the start of scale value is 0 kPa. ② 13.Close the stabilizing valve ③ ④ 14.Open the differential pressure valves ( ) completely. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 179: Commissioning With Vapor

    ② ① stabilizing valve is then opened, the pressure transmitter can be damaged by the flow of vapor. • Follow the specified procedure for commissioning. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 180 12.Close the stabilizing valve ③ ④ 13.Open the differential pressure valve completely. ⑦ 14.You can briefly open the blow-out valves to clean the line. Close before steam starts to leak. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 181: Repair And Maintenance

    WARNING Impermissible repair of explosion protected devices Danger of explosion in areas subject to explosion hazard. • Repair must be carried out by Siemens authorized personnel only. WARNING Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard.
  • Page 182 Danger of explosion in areas subject to explosion hazard. • Connect the device correctly after maintenance. • Close the device after maintenance work. Refer to Chapter "Connecting up (Page 63)". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 183 • Disconnect the device before you open the enclosure or remove enclosure parts. • Observe the special precautionary measures if maintenance is required while the device is live. Have maintenance work carried out by qualified personnel. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 184: Maintenance And Repair Work

    • Define a maintenance interval for recurring tests depending on the use of the device and your own experience. • The maintenance interval will vary from site to site depending on corrosion resistance. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 185: Checking The Gaskets

    – PROFIBUS: B_016: sensor error diagnostics in measured-value recording ● Grave hardware faults, the processor is not functioning. Displays: – Display: no defined display – PROFIBUS: slave not available SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 186: Changing The Measuring Cell And Application Electronics

    WARNING Dust layers above 5 mm Danger of explosion in hazardous areas. Device may overheat due to dust build up. • Remove dust layers in excess of 5 mm. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 187: Servicing The Remote Seal Measuring System

    • Do not use sharp or hard objects to clean the diaphragm. 11.4 Return procedure Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 188: Disposal

    Note Special disposal required The device includes components that require special disposal. • Dispose of the device properly and environmentally through a local waste disposal contractor. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 189: Interrupts, Error And System Alarms

    Output Unsure, Input condition "fail Check the data meas- safe" is fulfilled, the urement. Last usable value, parameterized safety value constant setting is set to "keep last valid value". SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 190 3, out- put 1), totalizer output 2) B_011 Secondary variable 3 Bad, Variable is not calcu- Correct the "transmitter lated type" setting. not connected, value constant SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 191 Only if the failure behavior of the totalizer function block has been set to "Operation". See also Error display (Page 74) Status display (Page 76) Status (Page 167) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 192: Errors

    F_008 Local operation blocked by Use SIMATIC PDM to set the SIMATIC PDM. "Local operation" parameter to "released". See also Status (Page 167) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 193: Technical Data

    ● SITRANS P DS III input (Page 194) ● SITRANS P410 input (Page 200) ● Output (Page 202) ● Measuring accuracy of SITRANS P DS III (Page 203) ● Measuring accuracy of SITRANS P410 (Page 211) ● Operating conditions (Page 214) ●...
  • Page 194: Sitrans P Ds Iii Input

    With 250mbar/25 kPa/3.6 psi measuring cells, the lower measuring limit is 750 mbar a/75 kPa a/10.8 psi a. The measur- ing cell is vacuum-tight down to 30 mbar a/3 kPa a/0.44 psi a. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 195 Lower measuring limit 0 mbar a/kPa a/psi a Upper measuring limit 100% of maximum span Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 196 14.5 … 435 psi a 653 psi a 1450 psi a Lower measuring limit 0 mbar a/kPa a/psi a Measuring cell with silicone oil filling • Measuring cell with inert liquid • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 197 3 kPa a + 2 kPa a • (ϑ - 60 °C)/°C cell 30 bar) (140°F < ϑ ≤ 212°F 0.44 psi a + 0.29 psi a • (ϑ - 108 °F)/°F (max. 185°F for measuring cell 435 psi)) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 198 0.6 ... 60 kPa 42 MPa 2.409 … 240.9 inH 6091 psi 16 … 1600 mbar 420 bar 1.6 ... 160 kPa 42 MPa 6.424 … 642.4 inH 6091 psi SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 199 2.5 ... 60 kPa 10 … 240 inH 53 … 1600 mbar 5.3 ... 160 kPa 021 … 640 inH 160 … 5000 mbar 16 ... 500 kPa 2.32 … 72.5 psi SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 200: Sitrans P410 Input

    100% of maximum span Start of scale value Between the measuring limits (fully adjustable) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 201 100% of maximum span Start of scale value Between the measuring limits (fully adjustable) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 202: Output

    Linearly increasing or linearly decreasing • Linear increase or decrease or root extraction increase (only for differential • pressure and flow rate) Bus physics – IEC 61158-2 Polarity-independent – SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 203: Measuring Accuracy Of Sitrans P Ds Iii

    Technical data 13.5 Measuring accuracy of SITRANS P DS III 13.5 Measuring accuracy of SITRANS P DS III Measuring accuracy (as per EN 60770-1) gauge pressure Reference conditions Rising characteristic curve • Start of scale value 0 bar/kPa/psi • Seal diaphragm stainless steel •...
  • Page 204 Technical data 13.5 Measuring accuracy of SITRANS P DS III Measuring accuracy (as per EN 60770-1) gauge pressure In 5 years ≤ (0.125 • r) % 16 bar/1.6 MPa/232 psi • 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi 400 bar/40 MPa/5802 psi In 5 years ≤...
  • Page 205 Technical data 13.5 Measuring accuracy of SITRANS P DS III Gauge pressure measuring accuracy, with flush mounted diaphragm Effect of auxiliary power supply In percent per change in voltage 0.005 % per 1 V Measured value resolution for 3 • 10...
  • Page 206 Technical data 13.5 Measuring accuracy of SITRANS P DS III Measuring accuracy (according to EN 60770-1) of pressure transmitter with PMC connection Reference conditions Rising characteristic curve • Start of scale value 0 bar/kPa/psi • Seal diaphragm stainless steel •...
  • Page 207 Technical data 13.5 Measuring accuracy of SITRANS P DS III Absolute pressure measuring accuracy (from gauge and differential pressure series) Linear characteristic curve • r ≤ 10 ≤ 0.1% 10 < r ≤ 30 ≤ 0.2% In percent per 28 °C (50 °F) Effect of ambient temperature •...
  • Page 208 Technical data 13.5 Measuring accuracy of SITRANS P DS III Differential pressure and flow rate measuring accuracy r ≤ 5 5 < r ≤ 10 10 < r ≤ 20 Linear characteristic curve • 20 mbar/2 kPa/0.29 psi ≤ 0.075 % ≤...
  • Page 209 Technical data 13.5 Measuring accuracy of SITRANS P DS III Differential pressure and flow rate measuring accuracy ≤ (0.15 • r + 0.1) % 20 mbar/2 kPa/0.29 psi • ≤ (0.075 • r + 0.1) % 60 mbar/6 kPa/0.87 psi •...
  • Page 210 Technical data 13.5 Measuring accuracy of SITRANS P DS III Differential pressure and flow rate measuring accuracy Effect of mounting position In pressure per change of angle ≤ 0.7 mbar/0.07 kPa/0.028 inH O per 10° incline (zero-point correction is possible with position error compensation)
  • Page 211: Measuring Accuracy Of Sitrans P410

    1 bar/100 kPa/14.5 psi • ≤ (0.025 • r + 0.125) % 4 bar/400 kPa/58 psi • 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 212 • 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 ps 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi Flow 25 ... 50% r ≤ 5 5 < r ≤ 30 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 213 30 bar/3 MPa/435.11 psi Effect of mounting position In pressure per change of angle ≤ 0.7 mbar/0.07 kPa/0.001015 psi per 10° incline (zero-point correction is possible with position error compensation) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 214: Operating Conditions

    NAMUR NE 21 Process medium conditions Process temperature • Cell Pressure Temperature range Measuring cell with sili- -40 … +100 °C (-40 … +212 °F) cone oil filling SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 215 85 °C (14 ... 185 °F)) Climate class Condensation Permitted IP66, IP68 Degree of protection in • accordance with EN 60 NEMA 4X Degree of protection in • accordance with NEMA Electromagnetic compatibility SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 216 In accordance with EN 61326 and NAMUR NE 21 Interference emission and inter- • ference immunity Process medium conditions -40 … +100 °C (-40 … +212 °F) Process temperature • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 217 In conjunction with dust explo- -20 … +60°C (-4 … +140°F) sion protection Rated conditions for level Installation conditions specified through the flange Installation instruction • Ambient conditions Ambient temperature • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 218: Construction

    • mat. no. 1.4408 Standard: Powder coating with polyurethane • Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane Stainless steel nameplate • Mounting bracket Steel or stainless steel SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 219 • Process connection Flanges as per EN and ASME • F&B and Pharma flange, clamp and threaded connectors • NEUMO BioConnect/BioControl • PMC connections for the paper industry • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 220 Measuring cell filling Silicone oil • Inert liquid • Process connection Standard Flush mounted • • • PMC Standard design • Minibolt Flush mounted • • • PMC Minibolt design • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 221 -18 NPT female thread and flat connection with -20 UNF fastening screw thread in accordance with EN 61518 or M10 fastening screw thread in accordance with DIN 19213 (M12 for PN 420 (MAWP 6092 psi)) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 222 Minus side Stainless steel, mat. no. 1.4404/316L Seal diaphragm • Stainless steel, mat. no. 1.4408 Pressure caps and locking • screws FPM (Viton) O-ring • Non-wetted parts materials • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 223 NPT adapter must be held in place while the NPT gland is screwed into the NPT adapter. 2.5 Nm (1.8 ft lb) Tightening torque for union nut made • of plastic SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 224: Display, Keyboard And Auxiliary Power

    12.5 mA Max. basic current • – Starting current ≤ basic current • – 15.5 mA Max. current in event of fault • Error shut-down electronics (FDE) – present SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 225: Certificates And Approvals

    = 24 V, I = 250 mA, P = 1.2 W Effective inner capacitance = 6 nF = 1.1 nF Effective inner inductance = 0.4 mH = 7 µH SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 226 Entity parameters As per "control drawing" A5E00072770A: = 30 V, I = 100 mA, P = 750 mW, R = 300 Ω, L = 0.4 mH, C = 6 nF SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 227: Profibus Communication

    • Addition with faulty value • Limit monitoring Upper and lower warning and alarm limits Physical block • Transducer blocks Transducer block "Pressure" • Calibration by applying two pressures SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 228 Parameterizable ramp function • Transducer block "Electronics temperature" • Simulation function Pressure measurement Constant value • • Parameterizable ramp function • Electronics temperature Constant value • • Parameterizable ramp function • SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 229: Dimension Drawings

    Process connection: G½B connection pin or oval flange ⑨ Mounting bracket (optional) Take an additional 20 mm (0.79 inches) thread length into account Not with "flameproof enclosure" type of protection SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 230 Minimum distance for rotating SITRANS P410 is only available as gauge pressure and differential pressure version. Image 14-1 Pressure transmitter SITRANS P DS III/P410 for absolute pressure, from the gauge pressure series, dimensions in mm (inches) SITRANS P DS III/P410 with PROFIBUS PA...
  • Page 231: Sitrans P Ds Iii/P410 For Differential Pressure, Flow Rate And Absolute Pressure From The Differential Pressure Series

    Dimension drawings 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series ① Electronics side, display (longer for cover with inspection window) ②...
  • Page 232 Dimension drawings 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series Take an additional 20 mm (0.79 inches) thread length into account Not with "flameproof enclosure" type of protection Not for "FM + CSA [IS + XP]" type of protection For Pg 13.5 with adapter, approx 45 mm (1.77 inches)
  • Page 233 Dimension drawings 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series ① Electronics side, display (longer for cover with inspection window) ② Connection end ③ Electrical connection: Pg 13.5 gland (adapter) •...
  • Page 234: Sitrans P Ds Iii/P410 For Level

    Dimension drawings 14.3 SITRANS P DS III/P410 for level 14.3 SITRANS P DS III/P410 for level ① Electrical connection: Pg 13.5 gland (adapter) • 2)3) M20 x 1.5 gland • ½-14 NPT gland • Han 7D/Han 8D plug • 2) 3) ②...
  • Page 235: Sitrans P Ds Iii (Flush-Mounted)

    For Pg 13.5 with adapter, approx 45 mm (1.77 inches) SITRANS P410 is only available as gauge pressure and differential pressure version. Image 14-4 Pressure transmitter SITRANS P DS III/P410 for level, including mounting flange, dimensions in mm (inches) 14.4 SITRANS P DS III (flush-mounted) ①...
  • Page 236: Note 3A And Ehdg

    The references to the approvals for "EHEDG" and "3A" refer to the respective process connections and are not device-specific. Please refer to the technical specifications of the respective pressure transmitter to see whether the desired certificate is available for your device/flange combination. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 237: Connections As Per En And Asme

    125 mm (4.9'') 1½'' 130 mm (5.1'') 1½'' 155 mm (6.1'') 150 mm (5.9'') 165 mm (6.5'') 190 mm (7.5'') 210 mm (8.1'') 230 mm (9.1'') 255 mm (10.0'') SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 238: F&B And Pharma Flange

    Approvals EHEDG DIN 11864-2 Form A - sterile collar flange ⊘D 94 mm (3.7'') Approx. 52 mm (2'') 113 mm (4.4'') 133 mm (5.2'') 159 mm (6.3'') Approvals EHEDG SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 239 Approvals EHEDG DIN 11864-3 Form A - sterile collar sockets ⊘D 77.5 mm (3.1'') Approx. 52 mm (2'') 91 mm (3.6'') 106 mm (4.2'') 130 mm (5.1'') Approvals EHEDG SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 240 Other connections Varivent connector ® ⊘D 40-125 84 mm (3.3'') Approx. 52 mm (2'') Approvals EHEDG Connection in accordance with DRD ⊘D 105 mm (4.1'') Approx. 52 mm (2'') SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 241 Approx. 52 mm (2'') 90.9 mm (3.6'') 106 mm (4.2'') 119 mm (4.7'') 2" 64 mm (2.5") 2½" 77.4 mm (3.0'') 3" 90.9 mm (3.6'') 4" 119 mm (4.7'') Approvals EHEDG SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 242: Pmc Style

    120 mm (4.7'') Approvals EHEDG 14.4.4 PMC Style Connections for the paper industry PMC Style Standard ⊘D – – 40.9 mm (1.6'') Approx. 36.8 mm (1.4'') M44x1.25 cap nut SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 243: Special Connections

    63 mm (2.5'') Approx. 170 mm (6.7'') SMS connectors SMS sockets with union nut ⊘D 2" 84 mm (3.3'') Approx. 52 mm (2.1'') 2½" 100 mm (3.9'') 3" 114 mm (4.5'') SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 244 Approx. 52 mm (2.1'') 2½" 91 mm (3.6'') 3" 106 mm (4.2'') IDF threaded sockets ⊘D 2" 64 mm (2.5'') Approx. 52 mm (2.1'') 2½" 77.5 mm (3.1'') 3" 91 mm (3.6'') SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 245: Spare Parts / Accessories

    Spare parts/accessories for SITRANS P DS III Selection and order data Order no. Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-..-..C.) For absolute pressure transmitter (7MF423.-..-..C.) 7MF4997-1AB Made of steel •...
  • Page 246 7MF4997-1AH Made of stainless steel • Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-..-..A., -..B. and -..D.) For absolute pressure transmitter (7MF423.-..-..A., -..B. and -..D.) 7MF4997-1AC Made of steel •...
  • Page 247: Order Data For Simatic Pdm

    For SITRANS P DS III FF • Network card 7MF4997-1DN For SITRANS P DS III • 7MF4997-1DP For SITRANS P DS III PA and DS III FF • Sealing rings for pressure caps made of 7MF4997-2DA FPM (Viton) • 7MF4997-2DB PTFE (Teflon) •...
  • Page 248: Ordering Data For Profibus Accessories

    In the Industrial Communication catalog (IK PI) you can find additional accessories that are required for communication with our devices and PROFIBUS. For the latest updates to this catalog, please visit the Industry Mall (https://mall.industry.siemens.com/). SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 249: Appendix

    Certificates (http://www.siemens.com/processinstrumentation/certificates) Certificates (China) Additional information for China The product is based on the standards QDSSC 001-2013, QDSSC 002-2013, QDSSC 003- 2013 and meets the requirements of CMC and CPA. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 250 Appendix A.2 Certificates (China) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 251 Appendix A.2 Certificates (China) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 252 Appendix A.2 Certificates (China) SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 253: Literature And Standards

    • Programmable • Target group: Manufacturers and suppliers of equipment IEC 61511 Functional safety - Safety systems for the process industry Section 1-3 Target group: Planners, constructors and users SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 254: Technical Support

    ● Service&Support (http://www.siemens.com/automation/service&support) where you will find support news, support documents including EDDs and software, and also support from experts. Additional Support If you have additional questions about the device, please contact your local Siemens representative. Find your local contact partner at: ● Partner (http://www.automation.siemens.com/partner) Documentation for various products and systems is available at: ●...
  • Page 255: List Of Abbreviations/Acronyms

    Unit for volume norml Standard liter Unit for volume Cubic meter Unit for volume normm Standard cubic meter Unit for volume Hectoliter Unit for volume inch Cubic inch Unit for volume SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 256 Manufacturer-independent standard for the networking of field devices, e.g. PLC, drives, or sensors. PROFIBUS can be used with the DP and PA protocols. SELV Safety extra-low voltage Safety extra-low-voltage SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 257: Functional Safety

    A safety-instrumented system (SIS) executes the safety func- tions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic unit/control system and final controlling element. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 258 List of abbreviations/acronyms B.2 Functional safety SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 259: Glossary

    Fault tolerance N means that a device can execute the intended task even when N faults exist. The device fails to execute the intended function in the case of N+1 faults. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 260 Generic Station Description → Link is a coupler with a variable transmission speed. The transmission speed is a maximum of 12 Mbps (DP) to 31.25 kbps (PA). Non-volatile memory EEPROM → SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 261 The achievable SIL is determined by the following safety-instrumented characteristics: ● Average probability of failure on demand (PFD ● Hardware fault tolerance (HFT) ● Safe failure fraction (SFF) srli2 srlin2 → SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 262 If you have used one of these functions, the measuring range will have changed. This changed, remaining measuring range is called the zero point offset. Refer to the Operation section for the corresponding modes of these functions. SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 263: Index

    Flange, 32, 49 Connector Flow, 23, 82 M12, 69 Function block Correct usage, (See improper device modifications) Analog input, 104, 114 CPU, 144 Function chart, 34 Customer Support Hotline, 254 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 264 Class-2 master, 38 Topology, 37 Measured value display, 74, 79 PROFIsafe, 141 Measured value display, 74, 79 Proof test, 133 Measuring cell Absolute pressure, 34 Differential pressure and flow rate, 31 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...
  • Page 265 Status code, 168, 189 Status code, 168, 189 Status display, 76 Structure, 24 Support, 254 Tank connection, 243 Test certificates, 15 Transducer block for electronics temperature, 96, 103 for pressure, 96 SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08...

This manual is also suitable for:

Sitrans p410

Table of Contents