Siemens SITRANS P Operating Instructions Manual page 193

Pressure transmitter
Hide thumbs Also See for SITRANS P:
Table of Contents

Advertisement

ID
Symbols
Message
A9
Event counter 2
Number underruns above
threshold
Maintenance required
AA
Device lifetime: Maintenance
demanded
Ab
Device lifetime: Maintenance
required
AC
Sensor lifetime: Maintenance
demanded
Ad
Sensor lifetime: Maintenance
required
AE
Service: Maintenance deman‐
ded
AF
Service: Maintenance required
AG
Calibration: Maintenance de‐
manded
AH
Calibration: Maintenance re‐
quired
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
Cause/Remedy
The number of underruns of the process value (set in parameters
"Lower limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
Forthcoming end of configured device's lifetime.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of configured device's lifetime.
Maintenance of device should be planned.
Forthcoming end of configured sensor's lifetime.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of configured sensor's lifetime.
Maintenance of device should be planned.
Forthcoming end of the configured service interval.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of the configured service interval.
Maintenance of device should be planned.
Forthcoming end of the calibration interval.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of the calibration interval.
Maintenance of device should be planned.
Diagnostics and troubleshooting
12.2 Diagnostic messages
193