Chapter 2 Installation

2.8 Connecting the Load Cells

2.9 Connecting Analog Outputs (AO1-AO6)

converter
2-12
Information for connecting the load cells is given in the appendix for each load cell type, see
table below.
Type of load cell
PFCL 301E
PFTL 301E
PFRL 101
PFTL 101
PFCL 201
PFTL 201
There are six analog outputs. Each output can be set either for voltage or current. Each analog
output from the digital/analog converter is a voltage. This is split into two outputs, one of which
is converted into a current output and the other kept as voltage. This is illustrated in
where for example X4:1 is the voltage output and X4:2 is the current output.
The allowed load current of the voltage output is max. 5 mA.
The allowed load resistance of the current output is max. 550 ohms.
Figure 2-12
shows AO1 connected for voltage output and AO2 for current output.
AO1
AO2
D/A-
AO3
12
bits
AO4
AO5
AO6
Figure 2-12. Connecting Analog Outputs
Cable diagrams in Appendix
B
C
D
E
F
G
PFEA113
X4:1
U
X4:2
I
X4:3
0 V
X4:4
U
X4:5
I
X4:6-10
See circuit diagram
for AO1 and AO2
X4:11-15
Figure 2-12
Max. 5 mA
U
Voltage
output
+
R
I
L
R
L
Max. 550 
U
Current
output
I
3BSE029382R0101 Rev C