9
CellsOnRoll 1
[2]
10
NominalLoad
[1 kN 225 lbs]
11
HangWeight
[XXXXXX] N
12
AnalogOut 1
[ZZ]
13
SetTensionAt10V
[XXXXXX] N
SetTensionAt20mA
[XXXXXX] N
14
FilterSettings
[250 ms 1.5Hz]
To
15
Operator
Menu
Finished
PressOk
3BSE029382R0101 Rev C
Section 3.8.1 Performing Fast Setup using Hanging Weights
Select the load cells (2, SingleSideA or SingleSideB) that
support the roll from the list with
Check the nominal load on the load cell name plate.
Select nominal load from the list with
Confirm with
1. Apply a known weight on the roll (see
2. Enter the value of the known weight. Confirm with
Select Voltage or Current from the list with
Confirm with
Voltage selected:
Enter the tension value corresponding to 10 V.
or
Current selected:
Enter the tension value corresponding to 20 mA.
Confirm with
Select filter setting (5, 15, 30, 75, 250, 750 or 1500 ms) from
the list with
FastSetUp of a system with one roll is now completed.
Press
menu.
Proceed with the FastSetUp for Roll 2. In step 4, select the
load cells (2, SingleSideC or SingleSideD) that support
Roll 2 from the list with
When using HangWeight the wrap gain value is calculated by the tension
electronics.
To be able to read the wrap gain value, go to menu EnterWrapGain of the desired
roll.
Tension Electronics PFEA113, User Manual
.
.
.
or
. Confirm with
to finish the fast setup and go to the operator
or
. Confirm with
NOTE
or
. Confirm with
or
.
Figure
3-1).
.
or
.
.
.
3-7
.