Chapter 2 Installation

2.13 Connecting Optional Units

2.13.1 Insulation Amplifier PXUB 201

2.13.2 Relay Board PXKB 201
2-14
Insulation amplifier PXUB 201 is used when galvanic insulation between input and output, or
between power supply and input/output, is required. See
PXUB
201.
Insulation amplifier PXUB 201 is intended for installation on a DIN-rail. The PXUB 201 is
connected by screw terminals.
PXUB 201 is normally supplied from the same +24 V DC supply that supplies the tension
electronics.
If PXUB 201 is mounted close to the terminal group, it is not necessary to use a screened cable
between the tension electronics and PXUB 201.
Example: AO1 (see also cable diagrams in Appendix B, C D, E, F or G)
PFEA113
AO1-AO6
Voltage Output
0 V
+24 V
0 V
Figure 2-16. Typical Connection of Insulation Amplifier PXUB 201
The digital outputs on PFEA113 are isolated as a group and should not be connected to more
than 24 V DC. In the following applications should relays be connected to the digital outputs:
The digital outputs must be isolated from each other.
The signal to the superior system is higher than 24 V DC or an AC signal.
The PXKB 201 is intended for mounting on a DIN-rail.
Table 2-4. Truth table PXKB 201.
Input signal to A1(+) and A2(-)
Digital input low (0 V)
Digital input high (24 V)
PXUB 201
X4
3
1 (Out U)
+
4
3
X1:1
7
+
X1:3
8
Section A.6.1 Insulation Amplifier
5
+
6
Connection between
11 and 12
11 and 14
3BSE029382R0101 Rev C