3BSE029382R0101 Rev C
Section 3.13.5 Handling of Measurement Data through Profibus
User Defined Scaling
The Profibus Measuring Range and Load Division can be adjusted according to user
preferences.
Profibus Measuring Range
Profibus Measuring Range (estimated web tension during normal operation) is a parameter
entered by the user. After the user has changed the Measuring Range value, changing Load cell
nominal load does not affect the Profibus scaling. The value of the least significant bit is defined
as Load Division.
Load Division
Load Division is the resolution that will be used on Profibus. The Load Division value is
calculated by PFEA113 and depends on the set measuring range.
The measuring range is divided into a limited number of divisions in the range 2001 - 5000.
The Load Division value = one division, contains only one significant digit (1, 2 or 5).
The Profibus can handle max. –32768 to +32767 (2
Example 1:
a.
Profibus Measuring Range (set by user) = 15 500 N
(estimated web tension during normal operation)
b.
Load Division calculated by PFEA113 = 5 N
(value of least significant bit on Profibus)
c.
Profibus Measuring Range/Load Division = 15500/5 = 3100
(the measuring range is divided into 3100 divisions)
Example 2:
If the Load Division, 5 N, in Example 1 is not sufficient, the Load Division can be adjusted.
This can be done by setting (decreasing) MeasuringRange in the Miscellaneous Menu to a
value that gives a sufficient Load Division (resolution).
a.
Measuring Range = 9000 N
(New, lower measuring rangesetting)
b.
New Load Division calculated by PFEA113 = 2 N
(New value of least significant bit on Profibus)
With the setting 9000 N in PFEA113 , the Profibus measuring range 0 – 15500 N (divided into
7750 divisions) can still be used, now with the Load Division (resolution) 2 N.
Normally, there is no need to set the measuring range lower than 1/3 of the estimated web
tension during normal operation.
The max. value that can be transmitted via Profibus, for a given Load Division, is:
Max. value = Load Division x 32767
Tension Electronics PFEA113, User Manual
16
) divisions.
3-45