A.6 Optional Units
A.6.1 Insulation Amplifier PXUB 201
3BSE029382R0101 Rev C
+
Input
+24 V
+24 V
Figure A-6. Insulation Amplifier PXUB 201
Table A-14. Data for Insulation Amplifier PXUB 201
Type
Power supply
Current consumption
Signal range
Input resistance
Max. load
Rise time
Ripple
Bandwidth (-3 dB)
Rated insulation voltage
Insulation test voltage
Dimensions (l × w × d)
Weight
Mounting
Tension Electronics PFEA113, User Manual
Data
20 - 253 V AC/DC
AC: 48 - 62 Hz, 2 VA
DC: 1 W
10 mA + external load, at 24 V
Input
Output
0 ± 10 V
0 ± 10 V
0 - 10 V
4 - 20 mA
0 - 5 V
4 - 20 mA
0 ± 10 V
0 ± 20 mA
0 - 5 V
0 - 20 mA
1 M at 10 V input
500 k at 5 V input
10 mA for voltage output
500  for current output
50 s or 50 ms, selectable
10 mV
p-p
10 kHz or 10 Hz
600 V, basic insulation
4 kV
99 × 12.5 × 111 mm
150 g
DIN-rail 35 mm
Section A.6 Optional Units
+