E5EC/E5EC-B/E5AC
Characteristics
Indication accuracy
(at the ambient temperature of
23°C)
Transfer output accuracy
Remote SP Input Type
Influence of temperature *2
Influence of voltage *2
Influence of EMS.
(at EN 61326-1)
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Proportional band (P) for cooling
Integral time (I) for cooling
Derivative time (D) for cooling
Control period
Manual reset value
Alarm setting range
Influence of signal source
resistance
Insulation resistance
Dielectric strength
Malfunction
Vibration
Resistance
Malfunction
Shock
Resistance
Weight
Degree of protection
Memory protection
Setup Tool
Setup Tool port
Approved standards
Standards
Conformed standards EN 61010-1 (IEC 61010-1), RCM
EMC
*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and L
thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: ±10°C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Refer to information on maritime standards in Shipping Standards on page 124 for compliance with Lloyd's Standards.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
*9. CX-Thermo version 4.67 or higher is required for the E5CC-B linear current output type.
48
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
±5% FS ±1 digit max.
CT input:
Potentiometer input: ±5% FS ±1 digit max.
±0.3% FS max.
±0.2% FS ±1 digit max.
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
10 to 55 Hz, 20 m/s
2
for 2 hrs each in X, Y, and Z directions
100 m/s
2
, 3 times each in X, Y, and Z directions
300 m/s
2
, 3 times each in X, Y, and Z directions
E5EC/E5EC-B: Controller: Approx. 210 g, Mounting Adapter: Approx. 4 g × 2
E5AC:
Controller: Approx. 250 g, Mounting Adapter: Approx. 4 g × 2
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
E5EC/E5AC: CX-Thermo version 4.5 or higher
CX-Thermo version 4.65 or higher *9
E5EC-B:
E5EC/E5EC-B/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a
E5EC/E5EC-B/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
models only.) *6, Lloyd's standards *7, EAC
EMI
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
USB port on the computer.*5
Cable are used together to connect to a USB port on the computer.*5
EN 61326-1 *8
EN 55011 Group 1, class A
EN 61326-1 *8
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-11