Omron E5 C Series Manual page 27

Digital temperature controller
Hide thumbs Also See for E5 C Series:
Table of Contents

Advertisement

Characteristics
Indication accuracy
(at the ambient temperature of 23°C)
Transfer output accuracy
Simple transfer output accuracy
Remote SP Input Type
Influence of temperature *3
Influence of voltage *3
Influence of EMS.
(at EN 61326-1)
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Proportional band (P) for cooling
Integral time (I) for cooling
Derivative time (D) for cooling
Control period
Manual reset value
Alarm setting range
Influence of signal source resistance
Insulation resistance
Dielectric strength
Malfunction
Vibration
Resistance
Malfunction
Shock
Resistance
Weight
Degree of protection
Memory protection
Setup Tool
Setup Tool port
*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*4. K thermocouple at -100°C max.: ±10°C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*7. CX-Thermo version 4.67 or higher is required for the E5CC-B linear current output type.
E5CC/E5CC-B
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
CT input:
±5% FS ±1 digit max.
E5CC-U
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1
Thermocouple:
Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
±0.3% FS max.
±0.3% FS max.*2
±0.2% FS ±1 digit max.
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *4
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
20 MΩ min. (at 500 VDC)
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
10 to 55 Hz, 20 m/s
2
for 2 hrs each in X, Y, and Z directions
100 m/s
2
, 3 times each in X, Y, and Z directions
300 m/s
2
, 3 times each in X, Y, and Z directions
E5CC/E5CC-B: Controller: Approx. 120 g, Mounting Adapter: Approx. 10 g
E5CC-U: Controller: Approx. 100 g, Mounting Adapter: Approx. 10 g
E5CC/E5CC-B: Front panel: IP66, Rear case: IP20, Terminals: IP00
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
E5CC: CX-Thermo version 4.5 or higher
E5CC-B: CX-Thermo version 4.65 or higher *7
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-B/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect
E5CC/E5CC-B/E5CC-U
to a USB port on the computer. *6
27