Size G 200 V
■ Connection of regenerative resistor
Internal
Size
regenerative
resistor
G
None
* Connectors X1 to X7 are secondary side circuits. (See [ 5. Appearance and name of each part ])
Insulation is required from the primary side power supply (power supply for motor brake).
Do not connect to the same power supply.
* Size G has a built-in dynamic brake. When using built-in dynamic brake, set switch XS to "1" side.
(Shipping setting is set to "1" side.)
*The indication of built-in dynamic brake resistance is up to 3 times in succession due to maximum allowable inertia,
stop from rated speed. If it is used under more conditions, the resistance may be broken and the dynamic brake may not operate.
* When exceeding the capacity of the built-in dynamic brake resistor, set the switch XS to "2" side and use the external dynamic
brake resistor. For connection, refer to the example of external dynamic brake connection.
* For details, refer to 7-1 Power connector XA, XB, XC, XD, and terminal block.
R2.0
In case of using the external
regenerative resistor
Between P and B:
Connect the external regenerative resistor
Connection of the Terminal
In case of not using the external
regenerative resistor
Between RB and B : Keep open
Industrial Device Solution Business Unit, Panasonic Corporation
No. SX-DSV03335 - 55-