9-5 Compliance with UL standard
Certified by the UL508C (file No. E164620) standard by observing the installation conditions 1, 2 below.
[1] Installation environment
Install the servo driver under the environment at pollution degree 2 or 1 stipulated in IEC60664-1.
Be sure to connect a UL-certified molded-case circuit-breaker (MCCB) or fuse to the main power supply.
Use copper conductor wires whose temperature rating is 75°C or higher.
[2] Short circuit current rating (SCCR)
This servo driver is compatible with power supply whose voltage is less than the maximum input voltage and
symmetrical current is 5,000 A or less.
[3] Branch circuit protection
Protect the branch circuit in accordance with the NEC (National Electrical Code) and the local standard.
[4] Load protection and overheating protection
The servo driver has a built-in function to protect against servo motor overload.
The overload protection function is operated based on the specified time limit characteristics when current has
reached 115% or more of the rating.
The servo motor is not provided with an overheating protection function. When it is necessary to satisfy the
NEC, implement overheating protection measures for the servo motor.
9-6 Radio waves act (South Korea) precautions
This servo driver is a Class A commercial electromagnetic radio wave generator not designed for home use.
The user and distributor should be aware of this fact.
[Reference translation]
Class A device (broadcast communication device for business use)
This product is an electromagnetic wave generating device for business use (Class A), which is intended for
the use in places other than household.
The distributor and the user should be attentive to this point.
(Applicable model: Servo Driver)
R2.0
Industrial Device Solution Business Unit, Panasonic Corporation
No. SX-DSV03335 - 82-