5 Installation
5.2

Mounting an outdoor temperature sensor

Fig.29
Fig.30
2
1
Z
1/2 Z
1 Optimum location
2 Possible position
44
C 340 / C 640
5.2.1
Avoid placing the outside sensor in a position with the following
characteristics:
5.2.2
Place the outside sensor in a position that covers the following
characteristics:
2
1
H
1/2 H (min. 2,5 m)

Positions to be avoided

Masked by part of the building (balcony, roof, etc.).
Close to a disruptive heat source (sun, chimney, ventilation grid, etc.).

Recommended positions

On a façade of the area to be heated, on the north if possible.
Half way up the wall of the area to be heated.
Under the influence of changes in the weather.
Protected from direct sunlight.
Easy to access.
1/2 H (min. 2,5 m)
H
H Inhabited height controlled by the sensor
Z Inhabited area controlled by the sensor