15.4 Maintenance of the air/flue gas drain connection flues

The connection pipes must be serviced at least once a year.
- Check that the pipe and the terminal are empty along their entire
length. This can be done by checking that the boiler is operating
correctly; a particular check will be made to ensure that the
maximum calorific flow can be reached. Turn over the boiler at full
output. Check the meter to ensure that the gas flow complies with
the maximum flow indicated on the technical specifications table.

15.5 Temperature sensor

The resistance values at the various temperatures are indicated in
the tables on the next page.
If a defective sensor is detected, it is possible to check the resistance
at the various temperatures using a measuring device with a
corresponding measurement range (e.g. a multimeter). In order to
obviate incorrect measurements, the sensor must be disconnected
from the connector bar in the boiler distribution panel.
Outside sensor resistance
Temperature
Resistance
(°C)
(ohm)
-20
2392
-16
2088
-12
1811
-8
1562
-4
1342
0
1149
Resistance of the NTC 12 sensor kOhm
(boiler water, boiler return water, flue gases)
Temperature
Resistance
(°C)
(ohm)
10
22800
20
14770
30
9800
40
6650
50
4610
15/02/2011 - 300014279-001-J
Temperature
Resistance
(°C)
(ohm)
4
984
8
842
12
720
16
616
20
528
24
454
Temperature
Resistance
(°C)
(ohm)
60
3250
70
2340
80
1710
90
1270
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
- Check the seal.
- Check the condensates evacuation device in the boiler and on the
pipe if used.
- Replace the leakproof seals and sections of pipe if these no longer
offer a perfect guarantee of leak tightness after being dismantled
during a maintenance operation (only for the visible part of the
pipe).
Resistance of the NTC 10 sensor kOhm
(Domestic hot water, Outlet B, Outlet C)
Temperature
Resistance
(°C)
(ohm)
0
32014
10
19691
20
12474
25
10000
30
8080
40
5372
15. Maintenance
Temperature
Resistance
(°C)
(ohm)
50
3661
60
2535
70
1794
80
1290
90
941
75