Dimensions Of Flue Gas Outlet Pipe; Length Of The Flue And Air Supply Pipes - DeDietrich C 340 Series Installation And User Manual

High-efficiency floor-standing gas boiler with diematic evolution scb-01, diematic evolution scb-10
Table of Contents

Advertisement

Tab.13
Overview of material properties
Version
Flue gas outlet
Material
Single-wall, rigid
Plastic
Stainless steel
Thick-walled,
aluminium
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
Fig.13
Dimensions of open connection
ød
1
7762666 - v.02 - 29092020
Material properties
With CE marking
(1)
Temperature class T120 or
(2)
higher
Condensate class W (wet)
(2)
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
4.5.3
Tab.14
150 mm
200 mm
250 mm
350 mm
AD-3001094-01
4.5.4
The maximum length of the flue and air supply vary per appliance type.
Consult the relevant chapter for the correct lengths.
If a boiler is not compatible with a specific flue system or diameter, it is
indicated with "-" in the table.
When using bends, the maximum flue length (L) must be shortened
according to the reduction table.
Use approved flue reducers for adaptation to another diameter.
With a room-ventilated system, only the flue is connected. The air supply
is not connected and will draw the combustion air directly from the
installation area.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof feed-throughs and common channels.
The materials used must comply with the prevailing regulations
and standards.
Air supply
Material
Plastic
Stainless steel
Aluminium

Dimensions of flue gas outlet pipe

Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
d
External dimensions of flue gas outlet pipe
1
Dimensions of pipe
d
(min-max)
1
149 - 151 mm
199 - 201 mm
249 - 251 mm
349 - 351 mm

Length of the flue and air supply pipes

Room-ventilated system (B
4 Preparation of installation
Material properties
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
, B
)
23
23P
C 340 / C 640
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents