Connecting The Power Cable - DeDietrich C 340 Series Installation And User Manual

High-efficiency floor-standing gas boiler with diematic evolution scb-01, diematic evolution scb-10
Table of Contents

Advertisement

Fig.59
Anode connector
TA
+ TA -
Tab.43
Power connection
Wire cross section
solid wire: 2.5 mm² (AWG 14)
stranded wire: 2.5 mm² (AWG 14)
stranded wire with ferrule: 2.5 mm² (AWG 14)
Fig.60

Connecting the power cable

3
L
N
7762666 - v.02 - 29092020
Connect the anode as follows:
+ Connection on the calorifier tank
- Connection on the anode
Caution
If the calorifier tank does not have a TAS anode, connect the
simulation anode (= accessory)
AD-4000005-02
5.8.5
Connecting the power cable
The power connection is located in the rear part of the control box. The
power connection is fitted with a 10AT fuse.
Danger of electric shock
Always turn off the main power before working on the electrical
connections.
Make sure the following requirements are met when connecting the power
cable:
1. Undo the quarter turn screw.
2. Remove the cover.
3. Connect the power cable to the connector block.
4. Close the cover.
5. Tighten the quarter turn screw.
2
1
AD-3001593-01
Stripping length
Tightening torque
7 mm
0.5 N⋅m
C 340 / C 640
5 Installation
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents