Relay Contact Ratings - GE VersaMax IC200PWR001 User Manual

Table of Contents

Advertisement

Relay Contact Ratings

Appendix
B
Mechanical Rating
Relay contacts are rated for 10
Electrical Rating
The relay contacts used in VersaMax modules meet Underwriters Laboratories'
Pilot Duty Rating for Control Circuits. Contact life depends on type of load and
current, as summarized in the following table.
Operating
Voltage
24 to 125 V AC
24 to 125 V AC
24 to 125 V AC
24 to 125 V AC
250 V AC
250 V AC
250 V AC
250 V AC
5 to 31 V DC
5 to 31 V DC
5 to 31 V DC
5 to 31 V DC
32 to 125 V DC
Power Factor = 0.4 minimum for AC inductive loads
Time Constant – 7mS for DC inductive loads
Installing suitable suppression across inductive loads enhances reliability. For
DC, a free-wheeling diode provides suitable suppression. For AC, an R-C filter
can be used.
GFK-1504N
7
operations.
Maximum Current for Load Type
Resistive
Inductive
2.0 A
0.35 A
1.00 A
1.5 A
0.20 A
0.8 A
0.10 A
2.0 A
0.15 A
1.00 A
1.0 A
0.6 A
2.0 A
0.70 A
2.00 A
1.1 A
0.25 A
0.7 A
0.10 A
0.2 A
not rated
Typical Contact
Life (operations)
300,000
100,000
500,000
1,000,000
180,000
30,000
500,000
1,000,000
200,000
50,000
500,000
1,000,000
300,000
B-1

Hide quick links: