GE VersaMax IC200PWR001 User Manual page 389

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Channels
Module ID
Isolation:
User input to logic and to
frame ground
Group to group
Channel to channel
LED indicators
Backplane current
consumption
External power supply:
Range
Current consumption
Thermal derating
Configuration parameter
Diagnostics
Compatibility
HW, FW vers.
FW release
Output Characteristics
Output current
Load characteristics:
Resistive
Capacitive
Inductive
Accuracy:
+25 deg C
0 to +60 °C
Resolution
Update rate per module
Channel-to-channel crosstalk
rejection
Output default
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m),
accuracy may be degraded an additional ±1%.
††
R
L(MAX)
GFK-1504N
Chapter 11 Analog Output Modules
Analog Output Module, 13 Bit Current, 8 Channels
8 single-ended, one group
FFFF9480
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
None
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
5V output: 50mA maximum
+18 to +30 V DC (including ripple)
2A inrush maximum
100 mA maximum (no load)
185 mA maximum (all 8 outputs at full scale)
None
Range, output default
Loss of User Side (Field) Power
PME programming
software
All
4 to 20mA (default)
0 to 20mA (configured with jumper)
0 to 800 Ω maximum
0.1µF maximum
0.5H maximum
± 0.3% of full scale (typical), ± 0.5% of full scale (max)
±1% of full scale (max)
4-20 mA: 5 counts = 2.5 uA (~12.7 bits)
0-20 mA: 4 counts = 2.5 uA (13 bits)
15 mSec maximum
70dB minimum
Hold Last State (default)
Low End of Range (configurable)
= (V
– 4V) / 20.38mA
FIELD PS
CPU
CPU
CPU
CPU
DBI
001
002
005
E05
001
CE
AB
AA
AA
2.1
2.1
2.1
2.1
††
11
IC200ALG326
EBI
GBI
PBI
001
001
001
AB
BF
CF
No
1.1
2.2
2.2
11-29

Hide quick links: