GE VersaMax IC200PWR001 User Manual page 165

Table of Contents

Advertisement

7
IC200MDL144
Input Module, 240 V AC Isolated 4 Points
Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and frame ground
Group to group
Point to point
Carrier Requirement
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Compatibility
HW,FW vers.
FW release
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Input impedance
7-12
VersaMax Modules, Power Supplies and Carriers User's Manual
4 Isolated Inputs
FFFF8802
500 V AC continuous; 2000 V AC for 1 minute
None
500 V AC continuous; 2000 V AC for 1 minute
Requires Box-Style, Barrier-Style or Spring-Style Carrier,
revision B or later. Cannot be used with Connector-Style
Carrier.
One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
5 V output: 30 mA maximum
None
None
Cimplicity
VersaPro
Control
ME
90
2.11
1.5
2.4
0 to 264 V AC (47 to 63Hz), 240 V AC nominal
155 to 264 V AC
0 to 40 V AC
7mA minimum
1.5mA maximum
1 cycle maximum
2 cycles maximum
38.5 kΩ (reactive) at 60Hz, typical
46.3 kΩ (reactive) at 50Hz, typical
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
GFK-1504N

Hide quick links: