Analog output module IC200ALG325 provides eight analog voltage outputs. The
output range can be either –10 V DC to +10 V DC (bipolar) or 0 V to +10 V DC
(unipolar).
An external 24V power supply is required for the outputs.
Intelligent processing for this module is performed by the CPU or Network
Interface Unit. The module receives 8 words of analog output data.
LED Indicators
The green FLD PWR LED indicates the presence of user-side power for the
analog field-side circuits.
The green OK LED is ON when backplane power is present to the module.
Diagnostics
The module reports a Loss of User Side Power fault for field-side circuits.
Configuration Parameters
The module has a default output range of -10 V DC to +10 V DC (bipolar), but
is easily set up with a jumper for the channels to output 0V to +10 V DC
(unipolar).
The module is also easily set up with a jumper for the outputs to either hold their
last states or default to 0V if backplane power or communications are
interrupted or the PLC is stopped. External user power must remain
uninterrupted.
Outputs remain in their default or last state until the module receives different
output data from the backplane, or until field power is removed.