Wiring for a Box-Style I/O Carrier or Spring-Style I/O Carrier
(IC200CHS002, IC200CHS005)
Field Wiring
Terminals
Each terminal on a Box-Style or Spring-Style I/O Carrier accommodates one
solid or stranded AWG #14 (avg. 2.1mm
2
0.36mm
cross section) wire, or two wires up to AWG #18 (avg. 0.86mm
section). Use copper wire rated for 90 degrees C. When inserting two wires in
the same position, the wires must be the same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8
Amps per each power and ground, and a voltage range of up to 264 V AC.
Voltage transients up to 300 V AC will not damage the carrier.
For a Box-Style I/O Carrier, recommended terminal torque is 0.37 to 0.45 ft-lbs.
The label provided with the module can be folded and inserted in the module's
transparent door.