Installing an Expansion Receiver Module
An Expansion Receiver Module (IC200ERM001 or 002) must be installed in the
leftmost slot of each VersaMax expansion rack.
1. Insert the label inside the small access door at the upper left corner of the
module.
2. Attach the module to the DIN rail at the left end of the expansion rack.
3. Select the expansion rack ID (1 to 7) using the rotary switch under the
access door at upper left corner of the module. Each rack must be set to a
different rack ID. With a single-ended cable (one expansion rack only), set
the Rack ID to 1.
4. Install a VersaMax Power Supply module on top of the Expansion Receiver.
Refer to the section, Installing a Power Supply.
5. Attach the cables. If the system includes an Expansion Transmitter Module,
attach the terminator plug to the EXP2 port on the last Expansion Receiver
Module.
6. After completing system installation, apply power and observe the module
LEDs.
EXP RX
2-8
VersaMax Modules, Power Supplies and CarriersUser Manual
PWR
SCAN
0
1
2
3
7
4
6
5
On indicates presence of 5VDC power.
Off indicates no 5VDC power.
Green indicates CPU/NIU is scanning I/O
in expansion racks.
Amber indicates not scanning.
Blinking or On indicates module is
communicating on expansion bus