GE VersaMax IC200PWR001 User Manual page 398

Table of Contents

Advertisement

11
IC200ALG327
Analog Output Module, 13 Bit Voltage 12 Channels
Cable Shield Connections
Shielded twisted pair cable is recommended for all of the analog channel
connections.
If the module is installed on a Terminal-style I/O Carrier (IC200CHS001, 002, or
005) or a Compact Terminal-style I/O Carrier (IC200CHS022, 025), the cable
shield can be connected directly to the carrier per the Field Wiring Table. An
Auxiliary I/O Terminal Strip (IC200TBM001, 002, or 005) can also be added to
the Terminal-style I/O Carriers to aid in grounding shields. Be sure to ground
the Auxiliary I/O Terminal Strip as well if you plan to use it for this purpose.
If the module is installed on a Connector-style I/O Carrier (IC200CHS003), the
cable shield can be connected directly to an Interposing Terminal
(IC200CHS011, 012, 015). Be sure to ground the Interposing Terminal. It is
recommended to use a shielded interposing cable as well between the
Interposing Terminal and the Connector Base. A custom shielded cable can be
made using the Connector kit (IC200ACC304). In addition, a custom shield
braid can be wrapped around standard Interposing Cables (IC200CBL105, 110,
120, 230). If this approach is used be sure to ground the braid.
All cable shield connections should be connected to earth ground and be kept
as short as practical. The power cable does not need to be shielded.
11-38
VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents