12
IC200ALG432
Analog Mixed Module, 12 Bit ± 10 V DC Input 4 Channels and Output 2 Channels
Count vs Output Voltage
Voltage
12
10
8
6
4
2
0
-2
4
-6
-8
-10
-12
-32000 -25600 --19200 12800 -6400 0
Voltage can be calculated using the following equation:
V
= ( (analog counts x 20.5) / 65535 )
out
The count value must be a multiple of 16. If the module receives a count
value that is not a multiple of 16, it rounds the value down to the closest
multiple of 16. For example:
12-24
VersaMax Modules, Power Supplies and Carriers User's Manual
6400 12800 19200 25600 32000
Count
Count
Voltage
16032
5.0150V
16040
5.0150V
16048
5.0200V
16 counts
= 5mV
5.0250V
5.0200V
16064
5.0150V
16048
5.0100V
16032
16016