Mixed Module, 24 V DC Positive Logic Input 20 Points / Output 12 Point /
(4) High-speed Counter, PWM, or Pulse Train Configurable Points
Module Data
The module provides 40 bits of bit input data and 13 words of word input data:
Bit
Inputs
(%I)
Word
Inputs
(%AI)
GFK-1504N
Chapter 13 Mixed Discrete/High-Speed Counter Module
1 - 20
Standard Inputs #1 to #20
21 - 24
Strobe Status #1 to 4
25 - 28
Preload Status #1 to 4
29 - 32
HSC Output Status #1 to 4
33 - 36
Pulse Train Complete #1 to 4
37
Home Complete
38 - 39
reserved
40
Status code present in Word Input 1
1
Module Status Code . Status Codes. See the section Command
Word Error Definitions at the end of this chapter.
2 - 5
Counts-per-Timebase #1 to 4.
6
Accumulator register #1.
7
Strobe register #1.
8
Accumulator register #2.
9
Strobe register #2.
10
Accumulator register #3.
11
Strobe register #3.
12
Accumulator register #4.
13
Strobe register #4.
13
IC200MDD841
13-21