GE VersaMax IC200PWR001 User Manual page 394

Table of Contents

Advertisement

11
IC200ALG327
Analog Output Module, 13 Bit Voltage 12 Channels
Analog output module IC200ALG327 provides twelve analog voltage outputs.
The output range can be either –10 V DC to +10 V DC (bipolar) or 0V to +10 V
DC (unipolar).
An external 24V power supply is required for the outputs.
Intelligent processing for this module is performed by the CPU or Network
Interface Unit. The module receives 12 words of analog output data.
LED Indicators
The green FLD PWR LED indicates the presence of user-side power for the
analog field-side circuits.
The green OK LED is ON when backplane power is present to the module.
Diagnostics
The module reports a Loss of User Side Power fault for field-side circuits.
Configuration Parameters
The module has a default output range of -10 V DC to +10 V DC (bipolar), but
is easily set up with a jumper for the channels to output 0V to +10 V DC
(unipolar).
The module is also easily set up with a jumper for the outputs to either hold their
last states or default to 0V if backplane power or communications are
interrupted or the PLC is stopped. External user power must remain
uninterrupted.
Outputs remain in their default or last state until the module receives different
output data from the backplane, or until field power is removed.
11-34
VersaMax Modules, Power Supplies and Carriers User's Manual
IC200ALG327
ANALOG OUTPUT
13BIT
VOLTAGE
12CH
1234567
814
OK
FLD
PWR
GFK-1504N