IC200ALG326
Analog Output Module, 13 Bit Current, 8 Channels
Wiring Example
Cable Shield Connections
Shielded twisted pair cable is recommended for all of the analog channel
connections.
If the module is installed on a Terminal-style I/O Carrier (IC200CHS001, 002, or
005) or a Compact Terminal-style I/O Carrier (IC200CHS022, 025), the cable
shield can be connected directly to the carrier per the Field Wiring Table. An
Auxiliary I/O Terminal Strip (IC200TBM001, 002, or 005) can also be added to
the Terminal-style I/O Carriers to aid in grounding shields. Be sure to ground
the Auxiliary I/O Terminal Strip as well if you plan to use it for this purpose.
If the module is installed on a Connector-style I/O Carrier (IC200CHS003), the
cable shield can be connected directly to an Interposing Terminal
(IC200CHS011, 012, 015). Be sure to ground the Interposing Terminal. It is
recommended to use a shielded interposing cable as well between the
Interposing Terminal and the Connector Base. A custom shielded cable can be
made using the Connector kit (IC200ACC304). In addition, a custom shield
braid can be wrapped around standard Interposing Cables (IC200CBL105, 110,
120, 230). If this approach is used be sure to ground the braid.
All cable shield connections should be connected to earth ground and be kept
as short as practical. The power cable does not need to be shielded.
11-32
VersaMax Modules, Power Supplies and Carriers User's Manual
Load
Load
Jumper installed =0 to 20mA
no jumper = 4 to 20mA
Jumper installed =0/4mA
no jumper = hold last state
-
24VDC
+
IOUT 1
RET 1
Shield
IOUT 4
RET 4
Shield
Range Jumper (B1)
JMP RET (B2)
Hold Jumper (B3)
Field Return
Field Power
GFK-1504N