Configurable Parameters
The default parameters of the RTD Input module can be used in many
applications. The module can be software-configured when it is installed in a
VersaMax PLC system or an I/O Station controlled by a NIU that is version 2.0
or above.
Module
Parameter
Analog Input
Data Length
Analog Input
Data
Reference
Line
Frequency
Channel
Active
Units
RTD Type
Wire Type
Alarm Low
Alarm High
Nominal
Resistance
Channel
Default Input
GFK-1504N
Chapter 14 Temperature Sensing Modules
Description
Word length of the module's
analog input data.
Starting offset for the
module's analog input data.
Specifies the line frequency.
Specifies if the channel
should return data and
alarms. If a channel is
"inactive" space is still
allocated for it.
The conversion type for each
RTD.
The type of RTD used for
each channel.
The type of field wiring for
each RTD.
The low alarm limit for the
channel, in engineering units.
The high alarm limit for the
channel, in engineering units.
An optional resistance
adjustment, in tenths of Ω.
Specifies analog input
returned upon error (including
open circuit errors).
Analog Input, 16 Bit RTD, 4 Channels
Default
4
user selectable
60 Hz
50 Hz, 60 Hz
Active
Inactive (off), Active (on)
tenths of Ω, tenths of °C, or tenths of °
Deg C
100 PT 385 10 PT, 25 PT, 25.5 PT 392, 100 PT 385, 100
PT 3902, 100 PT 392, 100 PT 3923, 100 PT
3916, 1K PT 375, 10 CU, 10 CU 427, 50 CU
427, 100 CU 427, 100 NI, 100 NI 618, 120 NI
672 604 NI/FE 518, 1K NI/FE 527, 500 Ohm,
3000 Ohm
3 Wire
3 Wire, 4 Wire
–2000
–32,768 to +32,767
8000
–32,768 to +32,767
0
0
14
IC200ALG620
Choices
0–4
F
0 to 3276.7
+ 3276.7
14-7