GE VersaMax IC200PWR001 User Manual page 266

Table of Contents

Advertisement

Mixed Module, Output 24 V DC Pos. Logic 0.5A Grouped w/ESCP 16 Points
Configuration Parameters
The module's basic input on/off response time is 0.5ms. For some applications, it
may be preferable to add additional filtering to compensate for conditions such as
noise spikes or switch bounce. Input filter times of 0ms, 1.0ms, or 7.0ms are
selectable through software configuration, for total response times of 0.5ms,
1.5ms, and 7.5ms respectively. The default is 1.0ms filter time (total response
time is 1.5ms).
Diagnostics
The module reports the presence of any overloaded points to the system on a per-
module basis. Amber LEDs indicate the overload conditions on a per-point basis.
Once the overload condition is removed, normal operation is resumed.
GFK-1504N
Chapter 9 Discrete Mixed Modules
/ Input 24 V DC Pos/Neg Logic Grouped 16 Points
9
IC200MDD842
9-7