IC200ALG430
Analog Mixed Module, 12 Bit Input Current 4 Channels and
Output Current 2 Channels
Count vs Output Current
The graph below shows the relationship between the output data that is
provided to the module from the backplane, and the actual output current. The
range spans between 4mA and 20mA.
mA
24
20
16
12
8
4
0
0
3200 6400
The following equation can be used to calculate specific output currents:
The count value must be a multiple of 8. If the module receives a count value
that is not a multiple of 8, it rounds the value down to the closest multiple of 8.
For example:
12-8
VersaMax Modules, Power Supplies and Carriers User's Manual
9600 12800 16000 19200 22400 25600 28800 32000
Count
I
= 4mA + (count/32760) x 16.38mA
out
Count
16000
16007
16008
8 counts =
4µA
32767
12.008mA
12.004mA
12.000mA
16008
16000
mA
12.000
12.000
12.004
12.012mA
16024
16016
GFK-1504N